Plan Review Notes
Plan Review Notes For Permit 21041010
Permit Number 21041010
Review Stop B
Sequence Number 2
Notes
Date Text
2022-10-25 18:07:49RESIDENTIAL(R3) ADDITION, ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT # 21041010
 101 GREYMON DR
  
 NOTE:
 CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC.
 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING.
 ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND
 METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 6 FEET
 BASED ON NAVD 88.
 THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL
 HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION
 IS 8 FEET.
 NOTE: PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR
 ELEVATION USING NAVD 88. NEED TO PROVIDE THE
 CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY
 SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW.
 CITY ORDINANCE 4729-17.
 SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE.
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 RESPONSE:
 PROPERTY APPRAISAL SUBMITTED WAS REVIEWED WITH ROBERT
 BROWN (BUILDING OFFICIAL). THE COST TO REBUILD THE
 HOUSE SEEMS TO BE TOO HIGH.
  
 ORIGINAL COMMENT:
 2-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK.
  
 ORIGINAL COMMENT:
 4- LOT DRAINAGE: PROPOSED WORK AFFECTS THE LOT DRAINAGE
 (DRIVEWAY AND REAR PAVERS). PROVIDE DRAINAGE PLAN
 SHOWING HOW THE SURFACE DRAINAGE IS KEPT WITHIN THE LOT
 AND NOT DIVERTED TO ADJACENT PROPERTIES. PROVIDE
 DRAINAGE PLAN SHOWING COMPLIANCE WITH THE FOLLOWING
 SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 5- ARCHITECT OF RECORD NEEDS TO SPECIFY COMPLETE DESIGN
 CRITERIA:
 A)OK. DONE BY NEW ENGINEER.
  
 ORIGINAL COMMENT:
 B)BUILDING EXPOSURE (NOTE: THIS BUILDING IS LOCATED IN
 EXPOSURE "D".
  
 RESPONSE:
 ENGINEER TO REVISE DESIGN CRITERIA ON SHEET S100. THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT "C".
  
 ORIGINAL COMMENT:
 C)ULTIMATE AND NOMINAL WIND SPEEDS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER.
  
 ORIGINAL COMMENT:
 D)COMPONENTS AND CLADDING DESIGN PRESSURES (DOORS AND
 WINDOWS)
 SEC. R301.2.1 FBC RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER.
  
 NEW COMMENT:
 E) ENGINEER TO REVISE DESIGN CRITERIA ON SHEET S100.
 THIS BUILDING IS NOT "OPENED" ENCLOSURE CLASSIFICATION.
 REVISE ALL INFORMATION AS REQUIRED.
  
 6- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK.
  
 ORIGINAL COMMENT:
 7- WINDOW SCHEDULE ON SHEET A-4 SPECIFIES "CASWELL
 WINDOWS". PROVIDE MANUFACTURER'S CUT SHEETS FOR
 CASEMENT WINDOW "H" SHOWING COMPLIANCE WITH BEDROOM
 WINDOW EGRESS CLEAR OPENINGS, INCLUDING CLEAR WIDTH
 OPENING.
 SEC. R310.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 NO INFORMATION SUBMITTED ON REVISED PLANS. PROVIDE
 COMPLIANCE WITH EMERGENCY EGRESS REQUIREMENTS FOR
 JUNIOR BEDROOM. CLEARLY SPECIFY TYPE AND SIZE OF
 WINDOWS AND PROVIDE MANUFACTURER'S CUT SHEETS FOR
 WINDOW TO BE USED AS EMERGENCY ESCAPE.
  
 8-11- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK.
  
 ORIGINAL COMMENT:
 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR
 LATER AS A DEFERRED SUBMITTAL).
  
 A)EXTERIOR DOORS. INSWING AND OUTSWING DOORS AS SHOWN
 ON PLANS.
  
 B)WINDOWS. ALL WINDOW TYPES AS SHOWN ON PLANS.
  
 C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 D)METAL ROOF. (IF ROOF IS TO BE REPLACED. PLANS ARE NOT
 CLEAR ON THIS).
  
 E)ROOFING UNDERLAYMENT. (IF ROOF IS TO BE REPLACED.
 PLANS ARE NOT CLEAR ON THIS).
  
 F)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 G)FRONT AND REAR PORCH PROPOSED ROOFING PANELS. SEE
 SHEET S103.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 14- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE.
 REPEAT COMMENT. NOT ADDRESSED.
  
 15-18- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK.
  
 NEW COMMENTS BASED ON REVISED DRAWINGS AND SCOPE OF
 WORK:
 19- BUILDING PLAN REVIEW NOTE ON SHEET A0.0 REFERS TO
 THE CITY OF CORAL GABLES. REVISE AS REQUIRED. PROVIDE
 CORRECT INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 20- PROPOSED PLAN ON SHEET S102:
 A)FLOOR PLAN IS MISSING INFORMATION FOR THE REAR PORCH.
 LOCATION, FOOTINGS, COLUMNS, ETC. SEC. 107.2.1 CITY
 AMENDMENTS. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 B)FLOOR PLAN IS MISSING INFORMATION FOR NEW FOOTINGS
 AND COLUMNS INFORMATION SHOWN ON SHEETS S104 AND S105
 FOR GARAGE INFILL WALL. SEC. 107.2.1 CITY AMENDMENTS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 C) CONSTRUCTION OF NEW BEAMS BETWEEN DINING ROOM AND
 KITCHEN AREA IS NOT CLEAR. PROPOSED FLOOR PLAN ON SHEET
 S102 SHOWS I BEAMS, WHILE INFORMATION ON SHEET S104 AND
 S105 SHOW DIFFERENT CONSTRUCTION MATERIALS. CLARIFY/
 COORDINATE TO AVOID CONFLICTS DELAYS. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: WOOD FRAME DETAIL ON SHEET S104 IS MISSING ALL
 STRUCTURAL CONNECTORS.
  
 D)THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE SPACE.
 TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR VAPOR
 BARRIER. ENGINEER OF RECORD TO PROVIDE SPECIFICATIONS
 FOR THE CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC.
 R506.2.3 FBC-RESIDENTIAL.
 ALSO, ENGINEER OF RECORD DOESN'T PROVIDE ANY
 INFORMATION OF HOW THE GARAGE SLAB IS RAISED TO THE
 EXISTING HOUSE LEVEL AS SHOWN ON SHEET A2.2. PROVIDE
 COMPLETE INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 21- SHEET S103:
 A)ENGINEER TO SPECIFY TYPE OF ROOF PANEL AND
 ATTACHMENT. (NOTE: PRODUCT APPROVAL WILL BE REQUIRED).
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 B)SECTION 1: ENGINEER TO SPECIFY LENGTH OF #9 SCREWS.
 HOW MUCH EMBEDMENT IS REQUIRED INTO THE 4X2 BATTEN?.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 C)SECTION 2: ENGINEER TO SPECIFY TYPE AND LENGTH OF
 1/2" SCREWS. HOW MUCH EMBEDMENT IS REQUIRED INTO THE
 EXISTING CONCRETE WALL. SEC. 107.2.1 CITY AMENDMENTS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 D)ENGINEER TO PROVIDE DETAIL/SPECIFICATIONS FOR
 FLASHING AT THE WALL INTERSECTION. SEC. R903.2
 FBC-RESIDENTIAL.
  
 E)ENGINEER TO SPECIFY ROOF PITCH. COORDINATE WITH TYPE
 OF ROOFING MATERIAL. SEC. R903.4 FBC-RESIDENTIAL.
  
 22)SHEET S104: ENGINEER TO PROVIDE SPECIFICATIONS FOR
 WELDING AT THE BASE AND TOP PLATES OF STELL COLUMNS.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301
 FBC-RESIDENTIAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,