| 2021-05-24 10:28:10 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. SEE NEW COMMENTS BELOW |
| | |
| | 1) PLEASE PROVIDE A RISER DIAGRAM SHOWING SERVICE |
| | CONDUCTORS, METER, PANELS, GROUNDING DETAILS. PLEASE |
| | INDICATE SIZE OF CONDUCTORS, PANELS, |
| | PANELS RATINGS, ETC. NEC 2017, FBC 107 |
| | |
| | 2) PLEASE PROVIDE LOAD CALCULATIONS FOR NEW SERVICE AND |
| | PANELS NEC 2017 |
| | |
| | 3) PLEASE PROVIDE UPDATED PANELS SCHEDULES FBC 107 |
| | |
| | 4) PLEASE SPECIFY AIC RATINGS OF SERVICE AND PANELS NEC |
| | 2017 |
| | |
| | 5) PLEASE SHOW LOCATION OF METER, DISCONNECTS, AND |
| | PANELS FBC 20 |
| | |
| | 6) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. |
| | PROVIDE CORRECTION. NEC 210.12; FBC RE E3902.16 (A NOTE |
| | WILL SUFFICE) |
| | |
| | 7) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE |
| | E4002.14, NEC 406.12 (A NOTE WILL SUFFICE) |
| | |
| | 8) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN |
| | EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL |
| | UTILIZE |
| | LAMPS WITH AN EFFICACY OF NOT LESS THAN 65 |
| | LUMENS-PER-WATT?. A NOTE WILL SUFFICE. FBC EC R404.1 |
| | |
| | 9) PLEASE CLARIFY CIRCUIT VOLTAGES FOR WASHER AND |
| | DRYER. DRAWING SEEMS TO INDICATE TWO 220 VOLTS |
| | CIRCUITS. NORMALLY WASHER IS ONLY 120 VOLTS. PLEASE |
| | SHOW CIRCUITS ON PANEL SCHEDULE. |
| | |
| | 10) PLEASE SHOW CIRCUIT FOR WATER HEATER AND SPECIFY |
| | CONDUCTOR SIZE AND BREAKER SIZE. |
| | |
| | |
| | SINCERELY, |
| | |
| | ENRIQUE QUINONEZ PE |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |