Plan Review Notes
Plan Review Notes For Permit 21041010
Permit Number 21041010
Review Stop B
Sequence Number 1
Notes
Date Text
2021-06-29 13:15:19RESIDENTIAL(R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 SECTION 606 FBC EXISTING BUILDING. CHAPTER 11
 FBC-EXISTING BUILDING.
 PERMIT # 21041010
  
 1- THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 6 FEET
 BASED ON NAVD 88.
 THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL
 HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION
 IS 8 FEET.
 NOTE: PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR
 ELEVATION USING NAVD 88. NEED TO PROVIDE THE
 CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY
 SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW.
 CITY ORDINANCE 4729-17.
 SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE.
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT
 FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED:
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 2-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 3- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. 1101.1
 FBC-EXISTING BUILDING AND SEC. R401.4 FBC-RESIDENTIAL.
  
 4- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 5- ARCHITECT OF RECORD NEEDS TO SPECIFY COMPLETE DESIGN
 CRITERIA:
 A)SPECIFY THE CURRENT CODE IN EFFECT, FBC-RESIDENTIAL
 7TH EDITION (2020).
 B)BUILDING EXPOSURE (NOTE: THIS BUILDING IS LOCATED IN
 EXPOSURE "D"
 C)ULTIMATE AND NOMINAL WIND SPEEDS.
 D)COMPONENTS AND CLADDING DESIGN PRESSURES.
 SEC. R301.2.1 FBC RESIDENTIAL.
  
 6- NOTE: SEPARATE FRAMING PLANS FROM THE PROPOSED FLOOR
 PLANS. PROVIDE COMPLETE FRAMING PLANS, DETAILS AND
 SPECIFICATIONS FOR:
 A)SECOND FLOOR FRAMING PLAN (NOTE: CHECK FLOOR JOIST
 SPAN AND JOIST SIZE).
 B)ADDITION ROOF FRAMING PLAN.
 C)EXISTING ROOF FRAMING PLAN MODIFICATIONS TO RECEIVE
 PROPOSED ADDITION.
 D) ALL EXTERIOR WALLS, INCLUDING WALL MEETING EXISTING
 ROOF.
 E)CUPOLA ROOF FRAMING PLAN AND WALL CONSTRUCTION.
 F)ALL EXTERIOR DOORS AND WINDOWS FRAMING DETAILS.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 G) SPECIFY AND SHOW ON FRAMING PLANS/DETAILS ALL BEAMS,
 COLUMNS, GIRDERS, FLOOR AND ROOF STRUCTURAL JOISTS.
 SPECIFY ROOF BOTTOM CHORD FRAMING MEMBERS (SEE 2 STORY
 WALL SECTION). SPECIFY CONNECTORS AT EACH END OF EACH
 FRAMING MEMBER. PROVIDE COMPLETE DETAILS/SPECIFICATIONS
 FOR EACH BEAM AND COLUMN.
 SEC. 107.2.5.3 CITY AMENDMENTS.
 SEC. R301.1.1 FBC-RESIDENTIAL.
  
 7- WINDOW SCHEDULE ON SHEET A-4 SPECIFIES "CASWELL
 WINDOWS". PROVIDE MANUFACTURER'S CUT SHEETS FOR
 CASEMENT WINDOW "H" SHOWING COMPLIANCE WITH BEDROOM
 WINDOW EGRESS CLEAR OPENINGS, INCLUDING CLEAR WIDTH
 OPENING.
 SEC. R310.2.1 FBC-RESIDENTIAL.
  
 8-TWO STORY WALL SECTION ON SHEET A-3:
 A)THE PROPOSED ADDITION IS GOING TO BE SUPPORTED BY
 EXISTING FIRST FLOOR WALL. WALL SECTION SHOWS AN
 EXISTING FOUNDATION OF 12" WIDE BY 24" DEEP FOOTING.
 THIS FOOTING TYPE AND SIZE IS NOT COMMON IN THIS AREA.
 ARCHITECT OF RECORD TO SPECIFY IF THIS FOOTING SIZE WAS
 FIELD VERIFIED. PROVIDE COMPLETE FOOTING SPECIFICATIONS
 (INCLUDING FOOTING REINFORCEMENT) AND PROVIDE
 CALCULATIONS SHOWING THAT IT'S ADEQUATE TO SUPPORT THE
 PROPOSED SECOND STORY MASONRY ADDITION. (NOTE:
 COORDINATE WITH SOIL TEST REPORT RECOMMENDATIONS AND
 GENERAL CONSTRUCTION NOTE #3 ON SHEET A-1).
 SEC. 107.2.1.2 CITY AMENDMENTS.
 SEC. R301.1.1 FBC-RESIDENTIAL.
  
 B)SECOND FLOOR EXTERIOR WALL CONSTRUCTION IS NOT CLEAR.
 WALL SECTION SHOWS WOOD FRAME CONSTRUCTION AND MASONRY
 CONSTRUCTION. IT IS NOT CLEAR WHAT AREAS ARE MASONRY
 AND WHAT AREAS ARE WOOD FRAME. REVISE PLANS AND WALL
 SECTIONS AS REQUIRED. CHECK SIZES OF WOOD FRAMED
 MEMBERS AND THICKNESS OF MASONRY WALL. HOW IS THE
 MASONRY WALL CONNECTED TO THE BOTTOM WALL?. HOW ARE THE
 ROOF WOOD FRAMING MEMBERS FASTENED TO THE WALL? HOW ARE
 THE WALL WOOD FRAMING MEMBERS FASTENED TO THE MASONRY
 WALL? HOW ARE THE FLOOR JOISTS CONNECTED TO THE WALL?.
 SPECIFY LEDGER SIZE AND FASTENING.
 SEC. 107.2.1.2 CITY AMENDMENTS.
 SEC. R301.1.1 FBC-RESIDENTIAL.
  
 C) SPECIFY SIZE OF CONTINUOUS SOFFIT VENT.
 SEC. R806.2 FBC-RESIDENTIAL.
  
 D)SPECIFY WALL INSULATION.
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 9- TYPICALLY, SEC. R806.2 FBC-RESIDENTIAL REQUIRES
 1/150 NET FREE VENTILATION AREA. GENERAL CONSTRUCTION
 NOTE ON SHEET A-1 SPECIFIES 1/300 NET FREE VENTILATION
 AREA. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE EXCEPTION OF SEC. R806.2
 FBC-RESIDENTIAL WHEN DESIGNING 1/300 NET VENTILATION
 AREA.
 NOTE: GENERAL CONSTRUCTION NOTE #28 SPECIFIES
 CONTINUOUS RIDGE VENT. THERE IS NOT RIDGE ON PROPOSED
 ROOF. SEE ROOF PLAN.
  
 10- WOOD FRAMED WALLS:
 A) NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1) FBC-RESIDENTIAL
  
 B)NEED TO SPECIFY TWO WATER RESISTIVE BARRIERS WHEN
 STUCCO IS APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3
 FBC-RESIDENTIAL.
  
 11-SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807.1
 FBC-RESIDENTIAL.
  
 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)EXTERIOR DOORS.
 B)WINDOWS.
 C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 D)METAL ROOF.
 E)ROOFING UNDERLAYMENT SPECIFIED ON TWO STORY WALL
 SECTION.
 F)ROOF VENTS SPECIFIED BY THE ARCHITECT. SEE PLANS.
 G)RIDGE ROOF VENT SPECIFIED BY THE ARCHITECT. SEE
 PLANS.
  
 13- SHEET A-1:
 A)REVISE/CLARIFY DESIGN LOADS SPECIFIED ON GENERAL
 CONSTRUCTION NOTES # 20 AND #44. SPECIFIED LOADS DON'T
 MATCH.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 B)REVISE USE GROUP SPECIFIED UNDER THE SETBACKS
 HEADING. THIS IS A SINGLE FAMILY RESIDENCE. CORRECT USE
 GROUP IS R3 NOT R2.
 SEC. 310.5 FBC-BUILDING.
  
 14- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 15- PROVIDE ROOF SHEATHING NAIL TYPE, SIZE AND SPACING
 AS REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: GENERAL CONSTRUCTION NOTE # 21 ON SHEET A-1
 DOESN'T COMPLY.
  
 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY CONSTRUCTION SHOWING COMPLIANCE WITH SEC.
 R311.7 FBC-RESIDENTIAL.
  
 17-SPECIFY CARBON MONOXIDE ALARM WITHIN ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 18- REVISE TOTAL PROPOSED AREA SPECIFIED BELOW THE
 PROPOSED FIRST FLOOR PLAN. TOTAL AREA IS NOT 2,530.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  