| Plan Review Notes For Permit 21040915 |
| Permit Number |
21040915 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-19 13:23:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NEED TO SHOW WIRES SIZES FOR SUB-FEEDERS 215.5 | | | | | | 2) NEED TO HAVE A CARBON MONOXIDE DETECTOR WITHIN 10' | | | OF SLEEPING AREAS FBC RESDIENTIAL R315 | | | | | | 3) NEED PANEL SCHEDULES. PROVIDE PANEL SCHEDULE | | | INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND | | | BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI | | | PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. NEC | | | 210.8, 210.12, 215.5, | | | | | | 4) PLAN NEEDS TO BE SIGNED BY DESIGNER OF RECORD OR THE | | | ELECTRICAL CONTRACTOR. 107.2.1 | | | | | | |
|