2021-04-19 13:23:09ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SHOW WIRES SIZES FOR SUB-FEEDERS 215.5
  
 2) NEED TO HAVE A CARBON MONOXIDE DETECTOR WITHIN 10'
 OF SLEEPING AREAS FBC RESDIENTIAL R315
  
 3) NEED PANEL SCHEDULES. PROVIDE PANEL SCHEDULE
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. NEC
 210.8, 210.12, 215.5,
  
 4) PLAN NEEDS TO BE SIGNED BY DESIGNER OF RECORD OR THE
 ELECTRICAL CONTRACTOR. 107.2.1
  
  