| 2021-04-28 09:32:59 | 04/28/21 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 2. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. THERE ARE NO SIZES ON PE PIPE, AND THE FIRE PIT CALL |
| | FOR 65 BTUS ON ISO AND SPECS IS 290 BTUS. PLEASE |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD |
| | SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN A 2 |
| | PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO 2 |
| | PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES PER THE 2020 FBC RES. SECS. |
| | G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. LIST THE |
| | BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. G2413. |
| | |
| | 5. WHERE IS THE DRYER LOCATED, AND IS IT IN A CLOSET, |
| | DOES LOVER DOOR, SO PLEASE SUBMIT CALCULATIONS FOR |
| | COMBUSTION AIR PER THE 2020 FBC RES. SEC. G2407.1 AND |
| | G2439.4 (CLOTHES DRYERS). |
| | |
| | 6. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| | |
| | 7. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC |
| | G2421.2. |
| | |
| | 8. PLEASE LABEL THE SHUT-OFF VALVE ON GAS ISOMERIC PER |
| | THE 2020 FBC RES. SEC. G2401.1.3. |
| | |
| | 9. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR |
| | APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC |
| | RES. SEC. G2419.2. |
| | |
| | 10. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3. |
| | BUILDING PERMITS VALUATIONS. |
| | |
| | 11. PLEASE SHOW THE DISTANCE OF THE LOCATION OF THE |
| | TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF |
| | ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 12. THIS UNIT REQUIRES CONDENSATE, AND IT NEEDS TO BE |
| | 1' AWAY FROM THE STRUCTURE PER THE 2017 FBC SEC. |
| | R318.5. PLEASE PUT NOT ON PLANS. |
| | |
| | 13. PIPES OR TANK-LEES NEED TO BE INSULATED WITH A |
| | MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3 PLEASE PUT |
| | A NOTE ON PLANS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |