| 2021-11-02 17:02:23 | RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21040876 |
| | |
| | ORIGINAL COMMENT: |
| | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 |
| | FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| | CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| | SUBMITTED. |
| | |
| | B)THERE ARE TWO DIFFERENT ENERGY CALCULATIONS |
| | SUBMITTED. ONE IS FORM 405-2020 PREPARED BY M. ABBOTT |
| | AND FORM R402-2020 PREPARED BY THE ARCHITECT. |
| | INFORMATION ON FORM R402-2020 DOESN'T MEET THE MINIMUM |
| | PRESCRIPTIVE REQUIREMENTS FOR THE GLAZED FENESTRATION |
| | (SHGC) AND THE A/C UNIT CAN NOT BE INSTALLED IN THE |
| | ATTIC. THIS FORM CAN NOT BE USED. PLEASE REMOVE THIS |
| | FORM. |
| | USE FORM R405-2020 AND MAKE SURE IS SIGNED BY THE OWNER |
| | OR ARCHITECT TO AVOID CONFLICTS/DELAYS. |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| | SUBMITTED. |
| | |
| | C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME, JURISDICTION NUMBER (THIS |
| | IS JURISDICTION #604700). SEC. R101.5.1.1.2 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| | SUBMITTED. |
| | |
| | D) |
| | E) |
| | |
| | E)DOOR INFORMATION SHOWS A 1FT X 5FT DOOR ON THE SOUTH |
| | SIDE. PLANS DON'T SHOW THIS DOOR. WHERE IS THIS DOOR |
| | LOCATED AT?. REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| | SUBMITTED. |
| | |
| | F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| | SUBMITTED. |
| | |
| | NOTE: |
| | WHEN RESUBMITTING, PLEASE SEPARATE THE ENERGY |
| | CALCULATIONS FROM THE A/C LOAD CALCULATIONS AND ANY |
| | OTHER A/C RELATED INFORMATION. A/C PLAN TO BE SUBMITTED |
| | UNDER THE DRAWINGS FOLDER. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | TO AVOID MORE DELAYS, PLEASE FEEL FREE TO CONTACT ME IF |
| | YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS, |