Plan Review Notes
Plan Review Notes For Permit 21040860
Permit Number 21040860
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-02 16:03:4411/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.1.1 AND A1.1.3;
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAIN PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 LAV OF THE OPEN SPACE IN THE WOMEN'S RESTROOM PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET A2.0.1;
  
 A. WOULD YOU PLEASE SHOW CLEAR FLOOR SPACE AND
 DIMENSIONS FOR THE LAV OF THE OPEN SPACE IN THE WOMEN'S
 RESTROOM PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON DETAIL FIVE, WOULD YOU PLEASE SHOW THE TOILET
 PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9"
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC.
 604.7.
  
 C. HANDICAP WATER CLOSET FLUSH CONTROL SHALL BE HAND
 OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM
 ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC SEC.
 604.9.5.
  
 D. IN AMBULATORY, THE GRAB BARS DO NOT MATCH THE
 DIMENSIONS SHOWN. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 E. IN THE AMBULATORY STALL, WOULD YOU PLEASE SHOW THE
 17 INCHES MINIMUM AND 19 INCHES MAXIMUM FROM THE
 SIDEWALL OR PARTITION IN THE AMBULATORY ACCESSIBLE
 TOILET COMPARTMENT SPECIFIED IN 604.8.2. WATER CLOSETS
 SHALL BE ARRANGED FOR A LEFT-HAND OR RIGHT-HAND
 APPROACH.
  
 F. WOULD YOU PLEASE SHOW THE PARTITION WALLS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. WOULD YOU, PLEASE NOTE THAT THE DOOR HARDWARE SHALL
 BE 34 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE FULLY
 OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE
 FROM BOTH SIDES PER THE 2020 FBC ACC. SEC. 404.2.7.
  
 3. ON SHEET A2.02;
  
 A. WOULD YOU PLEASE SHOW THE PARTITION WALLS NOT
 GREATER THAN 12 INCHES FROM AND EXTEND NOT LESS THAN 60
 INCHES ABOVE THE FINISHED FLOOR SURFACE PER THE 2020
 FBC 405.3.5PARTITIONS.
  
 B. ON DETAIL FIVE, WOULD YOU PLEASE SHOW THE TOILET
 PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9"
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC.
 604.7.
  
 C. HANDICAP WATER CLOSET FLUSH CONTROL SHALL BE HAND
 OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM
 ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC SEC.
 604.9.5.
  
 D. WOULD YOU, PLEASE NOTE THAT THE DOOR HARDWARE SHALL
 BE 34 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE FULLY
 OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE
 FROM BOTH SIDES PER THE 2020 FBC ACC. SEC. 404.2.7.
  
  
 4. ON SHEET A2.0.3;
  
 A. ON DETAIL ONE, WOULD YOU PLEASE SHOW THE BOTTOM OF
 THE DRINKING FOUNTAIN TO BE A MINIMUM OF 27" KNEE
 CLEARANCE PER THE 2020 FBC SEC. 306.3.
  
 B. ON DETAIL THREE, WOULD YOU PLEASE SHOW THE TOILET
 PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9"
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC.
 604.7.
  
 C. ON DETAIL FOUR AND EIGHT, WOULD YOU PLEASE SHOW THE
 BOTTOM OF THE LAV TO BE A MINIMUM OF 27" KNEE CLEARANCE
 PER THE 2020 FBC SEC. 306.3.
  
 D. WOULD YOU, PLEASE SHOW THE TOILET IS 16 INCHES TO 18
 INCHES TO THE CENTER PER THE 2020 FBC ACC SEC. 604.2
 LOCATION.
  
 E. WOULD YOU PLEASE SHOW THE 30 X 48 IN. CLEAR FLOOR
 SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2
 CLEAR FLOOR SPACE
  
 F. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 5. ON SHEET P-4.1;
  
 A. WOULD YOU PLEASE SHOW THE TRAP PRIMER FOR FLOOR
 DRAINS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 IT IS NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT
 IN THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A
 TEE FOR THE TWO RESTROOMS, AND TWO CHECK VALVES MAY BE
 USED ON EACH SIDE OF THE EXIT TEE TO DIRECT THE FLOW TO
 A TWO-LOOP IF PREFERRED FOR THE CORRECTION!
  
 C. THERE IS NO COLD WATER SHOWN IN THE RESTROOMS. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU, PLEASE SHOW THE HAMMER ARRESTOR FOR THE
 DRINKING FOUNTAIN PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THERE IS AN ON DETAIL FIVE THAT SAYS INSULATION FOR
 ? INCH, AND IT SHALL BE 1' PER TABLE C403.2.10 MINIMUM
 PIPE INSULATION THICKNESS. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR