| 2021-11-02 16:03:44 | 11/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A1.1.1 AND A1.1.3; |
| | A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE |
| | DRINKING FOUNTAIN PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE |
| | LAV OF THE OPEN SPACE IN THE WOMEN'S RESTROOM PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. ON SHEET A2.0.1; |
| | |
| | A. WOULD YOU PLEASE SHOW CLEAR FLOOR SPACE AND |
| | DIMENSIONS FOR THE LAV OF THE OPEN SPACE IN THE WOMEN'S |
| | RESTROOM PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. ON DETAIL FIVE, WOULD YOU PLEASE SHOW THE TOILET |
| | PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9" |
| | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC. |
| | 604.7. |
| | |
| | C. HANDICAP WATER CLOSET FLUSH CONTROL SHALL BE HAND |
| | OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC SEC. |
| | 604.9.5. |
| | |
| | D. IN AMBULATORY, THE GRAB BARS DO NOT MATCH THE |
| | DIMENSIONS SHOWN. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | E. IN THE AMBULATORY STALL, WOULD YOU PLEASE SHOW THE |
| | 17 INCHES MINIMUM AND 19 INCHES MAXIMUM FROM THE |
| | SIDEWALL OR PARTITION IN THE AMBULATORY ACCESSIBLE |
| | TOILET COMPARTMENT SPECIFIED IN 604.8.2. WATER CLOSETS |
| | SHALL BE ARRANGED FOR A LEFT-HAND OR RIGHT-HAND |
| | APPROACH. |
| | |
| | F. WOULD YOU PLEASE SHOW THE PARTITION WALLS PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | G. WOULD YOU, PLEASE NOTE THAT THE DOOR HARDWARE SHALL |
| | BE 34 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE FULLY |
| | OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE |
| | FROM BOTH SIDES PER THE 2020 FBC ACC. SEC. 404.2.7. |
| | |
| | 3. ON SHEET A2.02; |
| | |
| | A. WOULD YOU PLEASE SHOW THE PARTITION WALLS NOT |
| | GREATER THAN 12 INCHES FROM AND EXTEND NOT LESS THAN 60 |
| | INCHES ABOVE THE FINISHED FLOOR SURFACE PER THE 2020 |
| | FBC 405.3.5PARTITIONS. |
| | |
| | B. ON DETAIL FIVE, WOULD YOU PLEASE SHOW THE TOILET |
| | PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9" |
| | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC. |
| | 604.7. |
| | |
| | C. HANDICAP WATER CLOSET FLUSH CONTROL SHALL BE HAND |
| | OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC SEC. |
| | 604.9.5. |
| | |
| | D. WOULD YOU, PLEASE NOTE THAT THE DOOR HARDWARE SHALL |
| | BE 34 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE FULLY |
| | OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE |
| | FROM BOTH SIDES PER THE 2020 FBC ACC. SEC. 404.2.7. |
| | |
| | |
| | 4. ON SHEET A2.0.3; |
| | |
| | A. ON DETAIL ONE, WOULD YOU PLEASE SHOW THE BOTTOM OF |
| | THE DRINKING FOUNTAIN TO BE A MINIMUM OF 27" KNEE |
| | CLEARANCE PER THE 2020 FBC SEC. 306.3. |
| | |
| | B. ON DETAIL THREE, WOULD YOU PLEASE SHOW THE TOILET |
| | PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9" |
| | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC. |
| | 604.7. |
| | |
| | C. ON DETAIL FOUR AND EIGHT, WOULD YOU PLEASE SHOW THE |
| | BOTTOM OF THE LAV TO BE A MINIMUM OF 27" KNEE CLEARANCE |
| | PER THE 2020 FBC SEC. 306.3. |
| | |
| | D. WOULD YOU, PLEASE SHOW THE TOILET IS 16 INCHES TO 18 |
| | INCHES TO THE CENTER PER THE 2020 FBC ACC SEC. 604.2 |
| | LOCATION. |
| | |
| | E. WOULD YOU PLEASE SHOW THE 30 X 48 IN. CLEAR FLOOR |
| | SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR |
| | ACCESSIBLE DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2 |
| | CLEAR FLOOR SPACE |
| | |
| | F. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET? |
| | |
| | 5. ON SHEET P-4.1; |
| | |
| | A. WOULD YOU PLEASE SHOW THE TRAP PRIMER FOR FLOOR |
| | DRAINS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM |
| | IT IS NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT |
| | IN THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A |
| | TEE FOR THE TWO RESTROOMS, AND TWO CHECK VALVES MAY BE |
| | USED ON EACH SIDE OF THE EXIT TEE TO DIRECT THE FLOW TO |
| | A TWO-LOOP IF PREFERRED FOR THE CORRECTION! |
| | |
| | C. THERE IS NO COLD WATER SHOWN IN THE RESTROOMS. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. WOULD YOU, PLEASE SHOW THE HAMMER ARRESTOR FOR THE |
| | DRINKING FOUNTAIN PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | E. THERE IS AN ON DETAIL FIVE THAT SAYS INSULATION FOR |
| | ? INCH, AND IT SHALL BE 1' PER TABLE C403.2.10 MINIMUM |
| | PIPE INSULATION THICKNESS. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |