| 2021-06-17 16:46:24 | 2ND REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 21040859 |
| | 6/17/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | GUEST HOUSE PLUMBING. |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) MP1: THE GUEST HOUSE PLUMBING FLOOR PLAN AND |
| | ACCESSORY RISER DO NOT MATCH. BASED ON THE FLOOR PLAN, |
| | THE WASHING MACHINE DRAIN POINT OF CONNECTION TO THE |
| | MAIN SHOULD BE DOWN STREAM OF THE BATHROOMS- PLEASE |
| | CORRECT- SECTION 107.2.1 WPB. |
| | |
| | 2) MP1: INDICATE HOW HOT WATER WILL BE SUPPLIED TO THE |
| | GUEST HOUSE BATH FIXTURES- SECTION P2801.1 FBC P. |
| | |
| | 3) MP1: THE NEW PLUMBING PLAN SHOWS TWO DWELLINGS ON |
| | THE SAME LOT WHICH WILL REQUIRE WATER USERS TO INSTALL |
| | A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF |
| | DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL |
| | BE REQUIRED FOR THE WATER METER PER THE CITY OF WEST |
| | PALM CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION |
| | CONTROL PROGRAM. |
| | |
| | PLEASE NOTE ON THE PLAN THAT A FL. LICENSED PLUMBING |
| | CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| | WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |