| 2021-04-26 20:40:19 | ECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SEPARATE PERMIT REQUIRED FOR ACCESSORY STRUCTURE FBC |
| | 105.1 |
| | |
| | 2. NOTES SAY AFCI PROTECTION IN BEDROOMS ONLY, THAT IS |
| | NOT CODE COMPLIANT. AFCI PROTECTION MUST BE PER |
| | NEC210.12A&B |
| | NEW PANEL SCHEDULE DOES NOT SHOW AMPERAGE OF PANEL ( |
| | SHOULD SAY 200AMP) |
| | |
| | 3. SMOKE DETECTOR TO BE TIED INTO LOCAL LIGHTING |
| | CIRCUIT. CANNOT BE STAND ALONE.FBC-R APPENDIX J |
| | |
| | 4. NO LOAD CALC SHOWN FOR 100AMP PANEL IN ACCESSORY |
| | BUILDING NEC220 |
| | |
| | 5. NO SMOKE ALARMS SHOWN IN EITHER STRUCTURE. FBC-R 314 |
| | &315 |
| | |
| | 6. NEW PANEL SCHEDULE SHOWS 100AMP SUB PANEL BUT SUB |
| | PANEL IN MAIN STRUCTURE NOT SHOWN. |
| | |
| | 100AMP PANEL IN ACCESSORY BUILDING SHOWN TO HAVE OWN |
| | MAIN DISC OFF METER CAN?? PLEASE CLARIFY AND FIX PLANS |
| | AND PANEL SCHEDULE ACCORDINGLY. |
| | |
| | 7. MUST HAVE RECEPTACLE IN FRONT AND REAR OF DWELLING |
| | OUTSIDE. NEC 210.52E1 |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |