| 2021-05-07 09:25:04 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SHOW COMPLIANCE WITH FBC-R314 FOR REQUIRED SMOKE |
| | ALARMS AND R315 FOR CARBON MONOXIDE ALARMS. |
| | |
| | 2) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF AND THE |
| | EXTERIOR METAL DOORS WITH NO GLAZING. HI-LIGHT OR |
| | CIRCLE THE SPECIFIC ITEMS AND THEIR DESIGN PRESSURES IN |
| | THE PRODUCT APPROVAL THAT APPLY TO THIS PROJECT. MAKE |
| | SURE THAT THE DESIGN PRESSURES FOR THE PRODUCT MEET THE |
| | C&C PRESSURES THAT ARE SPECIFIED ON THE PLANS. FBC |
| | AMENDMENTS 107.3.4 - PROVIDE PRODUCT APPROVALS FOR |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 |
| | PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA |
| | NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM |
| | DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING |
| | MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL MULLIONS |
| | AND EXTERIOR DOOR TYPES. |
| | |
| | 3) PROVIDE THE FL COVER-SHEETS FOR THE FIXED WINDOW, |
| | FIXED CASEMENT WINDOW, EXTERIOR DOOR, CASEMENT WINDOW |
| | AND AWNING WINDOW. HI-LIGHT OR CIRCLE THE SPECIFIC |
| | ITEMS, SIZES, THEIR DESIGN PRESSURES, ETC. THAT APPLY |
| | TO THIS PROJECT ON THE PRODUCT APPROVAL. |
| | FBC AMENDMENTS 107.3.4 & 107.1.2 |
| | |
| | 4) HI-LIGHT OR CIRCLE THE SPECIFIC ITEMS, SIZES, THEIR |
| | DESIGN PRESSURES, ETC. THAT APPLY TO THIS PROJECT ON |
| | THE PRODUCT APPROVAL FOR THE STRUCTURAL MULLIONS. FBC |
| | 107.1.2 |
| | |
| | 5) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO ATTACH THE CLAY ROOF TILE. SUBMIT THE PRODUCT |
| | APPROVAL FOR THE ROOF TILE ADHESIVE THAT WILL BE USED. |
| | HI-LIGHT OR CIRCLE THE SPECIFIC ITEMS, SIZES, THEIR |
| | DESIGN PRESSURES, ETC. THAT APPLY TO THIS PROJECT ON |
| | THE PRODUCT APPROVAL. |
| | FBC AMENDMENTS 107.3.4 & 107.1.2 |
| | |
| | 6) HI-LIGHT OR CIRCLE THE SPECIFIC ITEMS, SIZES, THEIR |
| | DESIGN PRESSURES, ETC. THAT APPLY TO THIS PROJECT ON |
| | THE PRODUCT APPROVAL FOR THE ROOFING UNDERLAYMENT. FBC |
| | AMENDMENTS 107.1.2 |
| | |
| | 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |