Plan Review Notes
Plan Review Notes For Permit 21040844
Permit Number 21040844
Review Stop P
Sequence Number 2
Notes
Date Text
2022-06-06 14:48:302ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21040844
 6/6/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 2) FAILED. THE REQUESTED ENLARGED SITE SPECIFIC
 DRAWINGS AND DETAILS FOR THE PUBLIC RESTROOMS NOT
 PROVIDED. PLEASE COMPLY. WHERE PUBLIC BATHROOM
 FACILITIES ARE REQUIRED, PLEASE SHOW THE LOCATIONS ON
 THE FLOOR PLAN DRAWINGS AND PROVIDE SITE SPECIFIC FLOOR
 PLANS AND ELEVATION DRAWINGS THAT INCLUDE THE FOLLOWING
 ITEMS- FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSET FROM THE SIDE WALLS-
 SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 3) FAILED. REQUESTED DETAILS NOT PROVIDED. WHERE
 DRINKING FOUNTAINS ARE REQUIRED PLEASE REFER TO
 SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING
 FOUNTAIN INSTALLATION DETAILS AND ELEVATION VIEWS
 SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND
 SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN. CLEAR
 FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO THE
 FOUNTAIN- SECTION 602.2 FBC ACC.
  
 4) FAILED. G.0.03- REFER TO REQUIREMENT 7 FBC ACC:
 PLEASE INCLUDE THE REQUIRED COMPLIANCE WITH THE FAIR
 HOUSING ACT DESIGN MANUAL IN THE CODE INFORMATION, AND
 PROVIDE A LIST OF ALL UNITS THAT ARE COVERED UNDER THE
 ACT. THE INDIVIDUAL BATHROOMS SHALL BE DESIGNATED AS
 EITHER SPECIFICATION TYPE A OR B, AND ENLARGED
 DIMENSIONED DRAWINGS AND DETAILS IN ACCORDANCE WITH
 CHAPTER 7 OF THE MANUAL SHALL BE PROVIDED- SEE PAGE
 7.34 OF THE MANUAL. THE USABLE KITCHEN AND BATHROOM
 DESIGN SPECIFICATION REQUIREMENTS ARE LISTED UNDER
 REQUIREMENT 7 FBC ACC AND CHAPTERS 6 AND 7 OF THE
 MANUAL. BASED ON A LACK OF INFORMATION PROVIDED ON THE
 PLANS THE ACCESSIBILITY AND FAIR HOUSING REVIEWS ARE
 CURRENTLY STOPPED PENDING RESUBMITTAL OF REVISED PLANS.
 (SPECIFICATION A OR B SELECTION NOT PROVIDED HOWEVER IT
 APPEARS SPEC B HAS BEEN CHOSEN FOR THE BATHROOMS,
 PLEASE CONFIRM WITH A NOTE. PLEASE REVISE SHEETS A4.01-
 A4.08 TO PROVIDE THE DIMENSIONS OF THE CLEAR FLOOR
 SPACE DIAGRAMS SHOWN FOR THE FIXTURES- SEE PAGES 7.43-
 7.55 OF THE MANUAL.
  
 A) SHEETS A4.01- A4.08: PROVIDE TOILET AND BATHTUB GRAB
 BAR REINFORCEMENT DETAILS- PAGES 6.3- 6.16.
 B) A4.01- A4.08: PROVIDE THE CLEAR FLOOR SPACE
 DIMENSIONS FOR THE DIAGRAMS AT THE KITCHEN SINK AND
 APPLIANCES- PAGES 7.2- 7.6.
  
 5) FAILED. CIVIL PLANS NOT PROVIDED. NUMEROUS
 REFERENCES TO CIVIL PLANS HAVE BEEN MADE ON THE
 DRAWINGS HOWEVER PLANS HAVE NOT BEEN SUBMITTED. A
 COMPLETE PLUMBING REVIEW OF THE PROPOSED PROJECT CANNOT
 BE COMPLETED WITHOUT THE WATER AND SEWER CIVIL PLANS-
 SECTION 107.2.1 WPB. THE CIVIL PLANS SHALL SHOW THE
 LOCATIONS OF ALL POTABLE WATER BACKFLOW PREVENTERS
 WHICH ARE REQUIRED FOR THE NEW SERVICES TO THE
 BUILDINGS- SECTION 608.1 FBC P. PLEASE NOTE THAT FL.
 LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE
 PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN
 ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION.
  
 PLEASE NOTE DUE TO A CHANGE IN PROCESS, THE BACKFLOW
 PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF
 THE PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 12) FAILED. P301, 302, 303, 304, 305 (SECTIONS 1 & 15):
 THE NOTES INDICATE THAT BATHROOM WET VENTS ARE BEING
 DESIGNED HOWEVER THE DRAWINGS SHOW LAVATORY SINK DRAINS
 CONNECTING BELOW THE SOIL STACKS WHICH IS
 NON-COMPLIANT- SECTION 912.1.1 FBC P. THE PLAN NOTES
 HAVE CHANGED TO INDICATE BOTH A 3-INCH BATHROOM GROUP
 DRAIN AND A 4-INCH TOILET RISER- WHICH IS IT 3 OR
 4-INCH? THERE ARE NO INDIVIDUAL TOILET RISERS.
  
 A) FOR CLARIFICATION, PLEASE IDENTIFY THE LOCATIONS OF
 PIPING SECTIONS (1-15) ON SHEET P301- SEC. 107.2.1 WPB.
  
 16) FAILED. NOT PROVIDED. PLEASE NOTE IN ACCORDANCE WTH
 SEC. 1101.2 RAINWATER FROM ROOFS AND STORM WATER FROM
 PAVED AREAS, YARDS, COURTS ABMND COURTYARDS SHALL DRAIN
 TO AN APPROVED PLACE OF DISPOSAL. PROVIDE A ROOF
 DRAINAGE PLAN AND ISOMETRIC DRAWING- SECTIONS 1101-
 1108 FBC P. PLEASE INCLUDE CALCULATIONS, AND CIVIL
 PLANS THAT SHOW ROOF DRAIN PIPE CONTINUATIONS TO THE
 STORM DRAINS SYSTEMS FOR THE SITE.
  
 17) FAILED. NO NOTES PROVIDED IN RESPONSE. PROVIDE
 IRRIGATION PLANS- SEE APPENDIX F PART 1.B FBC P. THE
 PLANS MAY BE DEFERRED AND SUBMITTED UNDER SEPARATE
 PERMIT.
  
 18) FAILED. NO NOTES PROVIDED IN RESPONSE. PLEASE BE
 ADVISED THAT GREASE INTERCEPTORS MAY BE REQUIRED FOR
 THE RETAIL SPACES IF COMMERCIAL COOKING EQUIPMENT WILL
 BE INSTALLED- SECTION 1003.3.1 FBC P.
  
 NEW COMMENTS:
  
 1) SHEETS P0.01 & P0.02: PLEASE PROVIDE ENLARGED
 FIXTURE SCHEDULES (NOT NOTES) SHOWING THE MAKES AND
 MODELS OF THE PUBLIC AND RESIDENTIAL USE PLUMBING
 FIXTURES- SEC. 107.2.1 & 107.3.5.1.3 WPB.
  
 2) P0.01: THE HWR LINE SHALL BE ROUTED TO THE COLD
 WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER
 INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE- SEC. 607.2.2 FBC P.
  
 3) G1.01: PLEASE SHOW THE ACCESSIBLE ROUTE AND TRAVEL
 DISTANCE FROM THE MOST REMOTE BUSINESS/RETAIL OCCUPANCY
 TO THE PUBLIC BATHROOMS- SEC. 403.3 FBC P.
  
 4) P0.01 & P2.01: SHOW THE WATER HEATER DRAIN PAN LINES
 AND TERMINATION LOCATIONS- SEC- 504.7- 504.7.2 FBC P.
  
 5) PLEASE PROVIDE THE WATER HEATER EFFICIENCY DATA IN
 THE ENERGY/GAUGE COMPLIANCE REPORT- TABLE C404.2 FBC
 EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  