Plan Review Notes
Plan Review Notes For Permit 21040844
Permit Number 21040844
Review Stop P
Sequence Number 1
Notes
Date Text
2021-07-19 14:34:341ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21040844
 7/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G.0.03: PROVIDE PLUMBING FIXTURE CALCULATIONS
 FOR THE PROPOSED RESIDENTIAL AND ACCESSORY BUSINESS
 OCCUPANCIES- TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT
 SHOWS THE REQUIRED AND PROVIDED NUMBER OF PLUMBING
 FIXTURES. THE CURRENT PLANS DO NOT INDICATE THE
 LOCATIONS OF THE BUSINESS OCCUPANCY PLUMBING FIXTURES.
 PLEASE REVISE THE PLANS TO SHOW THE LOCATIONS OF ALL
 REQUIRED FIXTURES AND PROVIDE PLUMBING PIPING PLANS AND
 RISER DRAWINGS- SECTION 107.2.1 WPB.
  
 2) WHERE PUBLIC BATHROOM FACILITIES ARE REQUIRED,
 PLEASE SHOW THE LOCATIONS ON THE FLOOR PLAN DRAWINGS
 AND PROVIDE SITE SPECIFIC FLOOR PLANS AND ELEVATION
 DRAWINGS THAT INCLUDE THE FOLLOWING ITEMS- FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSET FROM THE SIDE WALLS-
 SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 3) WHERE DRINKING FOUNTAINS ARE REQUIRED PLEASE REFER
 TO SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE
 DRINKING FOUNTAIN INSTALLATION DETAILS AND ELEVATION
 VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS,
 AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN.
 CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO
 THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW THE
 LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2 PROTRUSION LIMITS.
  
 4) G.0.03- REFER TO REQUIREMENT 7 FBC ACC: PLEASE
 INCLUDE THE REQUIRED COMPLIANCE WITH THE FAIR HOUSING
 ACT DESIGN MANUAL IN THE CODE INFORMATION, AND PROVIDE
 A LIST OF ALL UNITS THAT ARE COVERED UNDER THE ACT. THE
 INDIVIDUAL BATHROOMS SHALL BE DESIGNATED AS EITHER
 SPECIFICATION TYPE A OR B, AND ENLARGED DIMENSIONED
 DRAWINGS AND DETAILS IN ACCORDANCE WITH CHAPTER 7 OF
 THE MANUAL SHALL BE PROVIDED- SEE PAGE 7.34 OF THE
 MANUAL. THE USABLE KITCHEN AND BATHROOM DESIGN
 SPECIFICATION REQUIREMENTS ARE LISTED UNDER REQUIREMENT
 7 FBC ACC AND CHAPTERS 6 AND 7 OF THE MANUAL. BASED ON
 A LACK OF INFORMATION PROVIDED ON THE PLANS THE
 ACCESSIBILITY AND FAIR HOUSING REVIEWS ARE CURRENTLY
 STOPPED PENDING RESUBMITTAL OF REVISED PLANS.
  
 5) NUMEROUS REFERENCES TO CIVIL PLANS HAVE BEEN MADE ON
 THE DRAWINGS HOWEVER PLANS HAVE NOT BEEN SUBMITTED. A
 COMPLETE PLUMBING REVIEW OF THE PROPOSED PROJECT CANNOT
 BE COMPLETED WITHOUT THE WATER AND SEWER CIVIL PLANS-
 SECTION 107.2.1 WPB. THE CIVIL PLANS SHALL SHOW THE
 LOCATIONS OF ALL POTABLE WATER BACKFLOW PREVENTERS
 WHICH ARE REQUIRED FOR THE NEW SERVICES TO THE
 BUILDINGS- SECTION 608.1 FBC P. PLEASE NOTE THAT FL.
 LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE
 PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN
 ACCORDANCE WITH SECTION 105.1WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION.
  
 6) P0.01: THE LOCATION OF THE THERMAL EXPANSION TANK IS
 NON-COMPLIANT FOR THE WATER HEATER SHOWN ON THE RIGHT
 SIDE OF THE DRAWING- SECTION 607.3 FBC P.
  
 7) P101, 102, 103: PLEASE PROVIDE DOMESTIC WATER RISER
 DRAWINGS FOR EACH OF THE FOUR BUILDINGS- SECTION
 107.3.5.1.3 WPB.
  
 8) P101, 102, 103: SHOW THE LOCATIONS OF MAIN SHUT OFF
 VALVES AT THE WATER RISERS TO THE UPPER FLOORS, AND AT
 THE ENTRANCES OF THE DWELLING UNITS- SECTION 606.1(4 &
 6) FBC P.
  
 9) P201, P301: PROVIDE THE DRAIN PIPE SIZES ON THE
 DRAWING- SECTION 710 FBC P.
  
 10) P301, 302, 303, 304, 305: PROVIDE DRAIN AND VENT
 PIPE SIZES ON THE DRAWINGS INCLUDING VENT STACKS, STACK
 VENTS, AND HEADERS- SECTIONS 904.1.2, 904.5, 906.1 FBC
 P.
  
 11) P301, 302, 303, 304, 305: THE WASHING MACHINE STACK
 VENT SHALL BE MINIMUM 3 IN. DIAMETER- SECTION 913.3 FBC
 P. PLEASE CORRECT THE NOTES ON THE DRAWING.
  
 12) P301, 302, 303, 304, 305 (SECTIONS 1 & 15): THE
 NOTES INDICATE THAT BATHROOM WET VENTS ARE BEING
 DESIGNED HOWEVER THE DRAWINGS SHOW LAVATORY SINK DRAINS
 CONNECTING BELOW THE SOIL STACKS WHICH IS
 NON-COMPLIANT- SECTION 912.1.1 FBC P.
  
 13) P301, P305 SECTION 14: THE KITCHEN SINK DRAIN SHALL
 NOT CONNECT TO THE WET VENT FOR THE BATHROOM- SECTIONS
 912.1 & 912.2 FBC P.
  
 14) P303 SECTION 5, P305 SECTION 15: DRAIN PIPE
 HORIZONTAL CONTINUATION SYMBOLS MISSING- SECTION 706.1
 FBC P.
  
 15) P3.01: IDENTIFY FUTURE FIXTURE DRAIN LOCATIONS AND
 INDICATE APPROVED CAPS WILL BE INSTALLED ON THE PIPE
 STUB OUTS- SECTION 704.4 FBC P.
  
 16) PROVIDE A ROOF DRAINAGE PLAN AND ISOMETRIC DRAWING-
 SECTIONS 1101- 1108 FBC P. PLEASE INCLUDE CALCULATIONS,
 AND CIVIL PLANS THAT SHOW ROOF DRAIN PIPE CONTINUATIONS
 TO THE STORM DRAINS SYSTEMS FOR THE SITE.
  
 17) PROVIDE IRRIGATION PLANS- SEE APPENDIX F PART 1.B
 FBC P. THE PLANS MAY BE DEFERRED AND SUBMITTED UNDER
 SEPARATE PERMIT.
  
 18) PLEASE BE ADVISED THAT GREASE INTERCEPTORS MAY BE
 REQUIRED FOR THE RETAIL SPACES IF COMMERCIAL COOKING
 EQUIPMENT WILL BE INSTALLED- SECTION 1003.3.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  