2021-07-16 09:54:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21040844
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 2) SHEET M0.01: PLEASE SHOW HOW THE GOODMAN SPLIT
 SYSTEM THAT IS LABELED COOLING ONLY WILL MEET THE
 HEATING REQUIREMENTS OF, FBC M 309.1
  
 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THESE
 UNITS. FBC M TABLE 403.3.1.1
  
 4) CONDENSATE FROM THE CONDENSING UNITS ON THE OUTDOOR
 BALCONIES MUST NOT DRAIN ON THE BALCONIES AS THIS WILL
 CAUSE A NUISANCE. FBC M 307.2.1
  
 5) PLEASE EXPLAIN THE USE OF BUILDING 3 & 4 AND THE
 NORTH & SOUTH POPUP SPACES. FBC 107.2.1
  
 6) PLEASE SHOW HOW THE UNITS ABOVE THE BATHROOM
 CEILINGS WILL BE ACCESSED FOR SERVICING. FBC M 306
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  