Plan Review Notes
Plan Review Notes For Permit 21040844
Permit Number 21040844
Review Stop E
Sequence Number 1
Notes
Date Text
2021-07-19 12:47:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PHONE OUTLET NEEDED IN EACH UNIT 800.154
  
 800.156 DWELLING UNIT COMMUNICATIONS OUTLET. FOR NEW
 CONSTRUCTION, A MINIMUM OF ONE COMMUNICATIONS OUTLET
 SHALL BE INSTALLED WITHIN THE DWELLING IN A READILY
 ACCESSIBLE AREA AND CABLED TO THE SERVICE PROVIDER
 DEMARCATION POINT
  
 2) FIRST FLOOR UNITS ARE REQUIRED TO HAVE AN RECEPTACLE
 OUTLET AT FRONT AND REAR OF UNIT. 210.52(E)(2)
  
 (2) MULTIFAMILY DWELLINGS. FOR EACH DWELLING UNIT OF A
 MULTIFAMILY DWELLING WHERE THE DWELLING UNIT IS LOCATED
 AT GRADE LEVEL AND PROVIDED WITH INDIVIDUAL EXTERIOR
 ENTRANCE/EGRESS, AT LEAST ONE RECEPTACLE OUTLET READILY
 ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M (61?2 FT)
 ABOVE GRADE LEVEL SHALL BE INSTALLED.
  
 3) FAULT CURRENT CALCULATION IS REQUIRED FOR SERVICE
 AND EQUIPMENT, AND LABELS ARE REQUIRED FOR THE
 EQUIPMENT. 110.9, 110,10, 110.24
  
 110.9 INTERRUPTING RATING. EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE AT LEAST
 EQUAL TO THE CURRENT THAT IS AVAILABLE AT THE LINE
 TERMINALS OF THE EQUIPMENT. EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT OTHER THAN FAULT LEVELS SHALL HAVE
 AN INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE AT
 LEAST EQUAL TO THE CURRENT THAT MUST BE INTERRUPTED.
  
 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT CURRENT
 RATINGS, AND OTHER CHARACTERISTICS. THE OVERCURRENT
 PROTECTIVE DEVICES, THE TOTAL IMPEDANCE, THE EQUIPMENT
 SHORT-CIRCUIT CURRENT RATINGS, AND OTHER
 CHARACTERISTICS OF THE CIRCUIT TO BE PROTECTED SHALL BE
 SELECTED AND COORDINATED TO PERMIT THE CIRCUIT
 PROTECTIVE DEVICES USED TO CLEAR A FAULT TO DO SO
 WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT OF
 THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE EITHER
 BETWEEN TWO OR MORE OF THE CIRCUIT CONDUCTORS OR
 BETWEEN ANY CIRCUIT CONDUCTOR AND THE EQUIPMENT
 GROUNDING CONDUCTOR(S) PERMITTED IN 250.118. LISTED
 EQUIPMENT APPLIED IN ACCORDANCE WITH THEIR LISTING
 SHALL BE CONSIDERED TO MEET THE REQUIREMENTS OF THIS
 SECTION.
  