| 2021-07-19 12:47:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) PHONE OUTLET NEEDED IN EACH UNIT 800.154 |
| | |
| | 800.156 DWELLING UNIT COMMUNICATIONS OUTLET. FOR NEW |
| | CONSTRUCTION, A MINIMUM OF ONE COMMUNICATIONS OUTLET |
| | SHALL BE INSTALLED WITHIN THE DWELLING IN A READILY |
| | ACCESSIBLE AREA AND CABLED TO THE SERVICE PROVIDER |
| | DEMARCATION POINT |
| | |
| | 2) FIRST FLOOR UNITS ARE REQUIRED TO HAVE AN RECEPTACLE |
| | OUTLET AT FRONT AND REAR OF UNIT. 210.52(E)(2) |
| | |
| | (2) MULTIFAMILY DWELLINGS. FOR EACH DWELLING UNIT OF A |
| | MULTIFAMILY DWELLING WHERE THE DWELLING UNIT IS LOCATED |
| | AT GRADE LEVEL AND PROVIDED WITH INDIVIDUAL EXTERIOR |
| | ENTRANCE/EGRESS, AT LEAST ONE RECEPTACLE OUTLET READILY |
| | ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M (61?2 FT) |
| | ABOVE GRADE LEVEL SHALL BE INSTALLED. |
| | |
| | 3) FAULT CURRENT CALCULATION IS REQUIRED FOR SERVICE |
| | AND EQUIPMENT, AND LABELS ARE REQUIRED FOR THE |
| | EQUIPMENT. 110.9, 110,10, 110.24 |
| | |
| | 110.9 INTERRUPTING RATING. EQUIPMENT INTENDED TO |
| | INTERRUPT CURRENT AT FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE AT LEAST |
| | EQUAL TO THE CURRENT THAT IS AVAILABLE AT THE LINE |
| | TERMINALS OF THE EQUIPMENT. EQUIPMENT INTENDED TO |
| | INTERRUPT CURRENT AT OTHER THAN FAULT LEVELS SHALL HAVE |
| | AN INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE AT |
| | LEAST EQUAL TO THE CURRENT THAT MUST BE INTERRUPTED. |
| | |
| | 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT CURRENT |
| | RATINGS, AND OTHER CHARACTERISTICS. THE OVERCURRENT |
| | PROTECTIVE DEVICES, THE TOTAL IMPEDANCE, THE EQUIPMENT |
| | SHORT-CIRCUIT CURRENT RATINGS, AND OTHER |
| | CHARACTERISTICS OF THE CIRCUIT TO BE PROTECTED SHALL BE |
| | SELECTED AND COORDINATED TO PERMIT THE CIRCUIT |
| | PROTECTIVE DEVICES USED TO CLEAR A FAULT TO DO SO |
| | WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT OF |
| | THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE EITHER |
| | BETWEEN TWO OR MORE OF THE CIRCUIT CONDUCTORS OR |
| | BETWEEN ANY CIRCUIT CONDUCTOR AND THE EQUIPMENT |
| | GROUNDING CONDUCTOR(S) PERMITTED IN 250.118. LISTED |
| | EQUIPMENT APPLIED IN ACCORDANCE WITH THEIR LISTING |
| | SHALL BE CONSIDERED TO MEET THE REQUIREMENTS OF THIS |
| | SECTION. |
| | |