Plan Review Notes
Plan Review Notes For Permit 21040844
Permit Number 21040844
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-19 15:35:53NEW 3 STORY APT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWINGS WITH THE WORDS "NOT FOR CONSTRUCTION"
 CANNOT BE APPROVED - PLEASE REMOVE THE COMMENT.
 2) BATHROOM CEILING HEIGHTS NEED TO COMPLY WITH FBC
 1208.2
 3) PLEASE SHOW STAIR WIDTHS FBC 1011.2
 4) PLEASE SHOW STAIR RISER HEIGHTS AND TREAD DEPTHS FBC
 1011.5.2
 5) CONSTRUCTION TYPE IS SHOWN AS IIB - PLYWOOD ROOF
 SHEATHING SHOULD BE SHOWN AS FIRE RETARDANT FBC 603.1
 6) CONSTRUCTION TYPE IS SHOWN AS IIB - CANNOT HAVE
 PLYWOOD AS PART OF THE FLOOR CONSTRUCTION FBC 602.2
 7) WOOD FLOOR SHEATHING WITHIN 18 INCHES OF THE GROUND
 SHALL BE OF NATURALLY DURABLE OR PRESERVATIVE-TREATED
 WOOD. FBC 2304.12.1.1JOISTS, GIRDERS AND SUBFLOOR.
 8) SECOND AND THIRD FLOOR EGRESS BALCONY - PLEASE SHOW
 THE DECKING TYPE AND CONNECTIONS TO FRAMING.
 9) SECOND AND THIRD FLOOR EGRESS BALCONY - MECHANICAL
 DRAWINGS SHOW AC UNITS ON THE EGRESS BALCONIES - PLEASE
 SHOW THAT THE REQUIRED EGRESS WIDTH REMAINS FBC 1005.4
 CONTINUITY.
 THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE MEANS OF
 EGRESS REQUIRED FROM ANY STORY OF A BUILDING SHALL NOT
 BE REDUCED ALONG THE PATH OF EGRESS TRAVEL UNTIL
 ARRIVAL AT THE PUBLIC WAY.
 10) DRAWING A7.32 SHOWS FIRE RATING INSTALLED OVER MATE
 LINES - PLEASE SHOW THE TYPE OF FIRE STOPPING TO BE
 INSTALLED.
 11) DRAWING A8.21 SHOWS WALL ASSEMBLY (VERTICAL
 ASSEMBLY) AND A NOTE ON THE DRAWING PERTAINING TO A
 HORIZONTAL ASSEMBLY - PLEASE CLARIFY.
 12) DRAWING S-1 SHOWS THE CODE VERSION USED FOR THE
 DESIGN AS 2017 FBC - SHOULD BE THE 2020 FBC - PLEASE
 REVISE.
 13) BUILDING DESIGN CALCULATIONS SHOWS THE 2017 FBC
 USED FOR DESIGN - SHOULD BE THE 2020 FBC - PLEASE
 REVISE.
 14) DRAWING S6 A - PLAN REFERS TO A NOTE NUMBER 9 -
 NOTE NUMBER 9 IS NOT ON THE DRAWING - PLEASE CLARIFY.
 15) DRAWING S6 B - PLAN REFERS TO NOTE NUMBER 8 - NOTE
 NUMBER 8 IS NOT ON THE DRAWING - PLEASE CLARIFY.
 16) DRAWING S6 C - NOTE NUMBER 9 SHOWS ROOF SHEATHING
 ATTACHED TO THE METAL FRAMING WITH NAILS - PLEASE
 CLARIFY METAL FRAMING ATTACHMENTS.
 17) PLEASE SHOW HOW THE WALLS BETWEEN UNITS COMPLY WITH
 THE REQUIRED MINIMUM STC RATINGS FBC 1207.2 (USING TEST
 REPORTS, WALL DESIGN MANUALS OR ANALYSIS FROM A DESIGN
 PROFESSIONAL )
 18) PLEASE SHOW HOW THE FLOOR/CEILING SYSTEMS COMPLY
 WITH THE REQUIRED MINIMUM STC AND IIC RATINGS FBC
 1207.2 AND 1207.3 (USING TEST REPORTS OR ANALYSIS FROM
 A DESIGN PROFESSIONAL )
 19) PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.2 (UNLESS THE PRODUCT APPROVAL NUMBER IS SHOWN ON
 THE DRAWINGS)
 20) PRODUCT APPROVAL (FL14724 - R10) HAS BEEN REVISED
 PLEASE PROVIDE THE REVISED ADDITION (FL14724 - R11).
 21) PRODUCT APPROVAL FOR THE SWING DOOR (FL11218 - R4)
 SHOWS ANCHORAGE TO A CONCRETE SUBSTRATE ONLY - PLEASE
 PROVIDE ATTACHMENT TYPES AND SPACING FROM THE DESIGN
 PROFESSIONAL. FBC WPB 107.2
 22) PRODUCT APPROVAL FOR THE LOW SLOPE ROOFING (FL17491
 - R5) = NEED TO CHOOSE A ROOFING SYSTEM IN THE PRODUCT
 APPROVAL THAT SHOWS THE REQUIRED WIND DESIGN PRESSURE -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE ADDITIONAL
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND
 PRESSURE THEN THE CHOSEN ROOFING SYSTEM - SEE NOTES ON
 THE PRODUCT APPROVAL.
 23) PLEASE SHOW THE BUILDING SQUARE FOOTAGE FOOTPRINT.
 24) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES).
 25) PLEASE PROVIDE A SURVEY SEC.94-76(A)(2) OF THE
 ZONING AND LAND DEVELOPMENT CODE.
 26) PLEASE SHOW THE GROUND FLOOR UNITS TO MEET FBC FHA
 REQUIREMENT 6 -REINFORCED WALLS FOR GRAB BARS. SHOW
 LOCATIONS AND BACKING DETAILS.
 27) PLEASE SHOW THE GROUND FLOOR UNITS TO MEET FBC FHA
 REQUIREMENT 7 -USABLE KITCHENS AND BATHROOMS. SHOW THE
 REQUIRED CLEAR FLOOR SPACE ON THE UNIT FLOOR PLANS. (A)
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 THAT ALLOWS A PARALLEL APPROACH BY A PERSON IN A
 WHEELCHAIR IS PROVIDED AT THE RANGE OR COOKTOP AND SINK
 AND EITHER A PARALLEL OR FORWARD APPROACH IS PROVIDED
 AT OVEN, DISH WASHER, REFRIGERATOR/FREEZER OR TRASH
 COMPACTOR. (SEE FIGURE FHAG-6) - - (2)USABLE BATHROOMS.
 TO MEET THE REQUIREMENTS OF SECTION 100.205(C)(3)(IV)
 EITHER.
 ALL BATHROOMS IN THE DWELLING UNIT COMPLY WITH OPTION
 2, OR THE PROVISIONS OF PARAGRAPH (A): OR
 AT LEAST ONE BATHROOM IN THE DWELLING UNIT COMPLIES
 WITH THE PROVISIONS OF PARAGRAPH (B), AND ALL OTHER
 BATHROOMS AND POWDER ROOMS WITHIN THE DWELLING UNIT
 MUST BE ON AN ACCESSIBLE ROUTE WITH USABLE ENTRY DOORS
 IN ACCORDANCE WITH THE GUIDELINES FOR REQUIREMENTS 3
 AND 4.
 28) PLEASE SHOW THE KITCHEN DIMENSIONS TO COMPLY WITH
 FBC FHA REQUIREMENT 7 (1) (B)CLEARANCE BETWEEN COUNTERS
 AND ALL OPPOSING BASE CABINETS, COUNTERTOPS, APPLIANCES
 OR WALLS IS AT LEAST 40 INCHES.
 29) PLEASE SHOW THE COMPONENT WIND DESIGN PRESSURES FOR
 THE OPENINGS AND ROOFING - FBC 1603.1.4 WIND DESIGN
 DATA. (5).DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF
 (KN/M2).
 30) DRAWING G0.03 HAS A STATEMENT "DESIGN IS COMPLIANT
 WITH THE 2017 FBC ACCESSIBILITY CODE (SHOULD BE 2020
 FBC ACCESSIBILITY) PLEASE CORRECT.
 31) PLEASE PROVIDE DETAILS FOR THE "TEXTILE FACADE
 SYSTEM" TO COMPLY WITH THE WIND LOADS FBC 1609
 32) PLEASE PROVIDE DETAILS FOR THE "MURAL PANEL FACADE
 SYSTEM" TO COMPLY WITH THE WIND LOADS FBC 1609
 33) FBC WPB107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 34) SEPARATE PERMITS ARE REQUIRED FOR PARKING LOT,
 DUMPSTER ENCLOSURES, FENCES, - PLEASE ACKNOWLEDGE THIS.