Plan Review Notes
Plan Review Notes For Permit 21040824
Permit Number 21040824
Review Stop E
Sequence Number 1
Notes
Date Text
2021-04-28 09:07:35FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) CURRENT FBC AND NEC CODES IN EFFECT ARE FBC 2020 7TH
 EDITION AND NEC 2017. PLEASE UPDATE YOUR CODE
 REFERENCES ACCORDINGLY.
  
 2) E-200 (ELECTRICAL GENERAL NOTES). NEW FBC ENERGY
 CODE 2020 7TH EDITION R404.1 HAS BEEN CHANGED TO:
  
 "NOT LESS THAN 90 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LUMINAIRES SHALL HAVE
 AN EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL
 UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65
 LUMENS-PER-WATT?.
  
 PLEASE UPDATE YOUR NOTES
  
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved