2021-05-25 13:42:02ROOF PRODUCT APPROVALS SUBMITTAL, SECOND BUILDING
 REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 SUBMITTAL #21040752
  
 1- OK.
  
 2- ROOF TILE AND ROOF TILE ADHESIVE PRODUCT APPROVALS
 SUBMITTED. CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED
 BY CITY POLICY FOR ALL ROOFING PERMITS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC R301.2.1
 FBC-RESIDENTIAL.
 NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "D". SEE
 STRUCTURAL DRAWING S-2. COORDINATE WITH DESIGNER OF
 RECORD TO AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 ROOF TILE NOA 18-0509.17 SUBMITTED WAS MARKED ON PAGE 5
 OF 9 WITH TILE BOND PADDY OF 13.9 GRAMS. THE MINIMUM
 ATTACHMENT RESISTANCE FOR THIS PADDY SIZE IS 31.3
 (FT-LBF). THIS BUILDING IS LOCATED IN EXPOSURE "D". SEE
 STRUCTURAL DRAWING S-2. USING TABLE 2A OF THE FRSA
 MANUAL (5TH EDITION REVISED) AS A REFERENCE I FOUND
 THAT FIELD TILE REQUIRES A MINIMUM OF 39.4 (FT-LBF)
 JUST FOR THE FIELD TILE. THEREFORE, SELECTED PADDY SIZE
 DOESN'T WORK. NEED TO SELECT A PADDY SIZE THAT WILL
 WORK FOR ALL ROOF ZONES, INCLUDING THE PERIMETER AND
 CORNER ROOF ZONES.
 R301.2.1 FBC-RESIDENTIAL.
  
 3- DESIGNER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT
 APPROVAL L ONCE IT IS REVISED.
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 REMAINDER:
 THIS PROJECT WAS APPROVED WITH PROVISO. PLEASE PROVIDE
 ALL THE REQUIRED INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. SEE COPY OF
 PROVISO BELOW.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE AND SPECIFY FASTENING. IF USING SCREWS,
 SPECIFY SIZE & NUMBER.
 B)ROOF TILE ADHESIVE IF SPECIFIED ABOVE.
 C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. NOTE: RAS
 117 CALCULATIONS IF REQUIRED.
 D)ENTRY DOOR.
 E)LAUNDRY DOOR.
 F)SLIDING GLASS DOORS.
 G)FIXED WINDOWS.
 H)HORIZONTAL SLIDING WINDOWS.
 I)CASEMENT WINDOWS.
 I)OVERHEAD GARAGE DOOR.
  