| 2021-05-13 16:18:40 | ROOF PRODUCT APPROVALS SUBMITTAL, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | SUBMITTAL #21040752 |
| | |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R24: |
| | THIS BUILDING IS LOCATED IN EXPOSURE "D". SEE |
| | STRUCTURAL DRAWING S-2. THE DESIGN PRESSURE OF SELECTED |
| | ASSEMBLY W-65 IS 105 PSF. THE DESIGN PRESSURE FOR |
| | COMPONENTS AND CLADDING ON ROOF ZONE #3 IS HIGHER THAN |
| | 105PSF. NEED TO PROVIDE SIGNED AND SEALED RAS 1117 |
| | CALCULATIONS. SEE NOTE #9 ON PAGE 3 OF 74 OF THIS |
| | PRODUCT APPROVAL OR SELECT ANOTHER ASSEMBLY THAT MEETS |
| | THE DESIGN PRESSURES FOR ALL ROOF ZONES. COORDINATE |
| | WITH DESIGNER OF RECORD TO AVOID CONFLICTS/DELAYS. |
| | |
| | 2- ROOF TILE AND ROOF TILE ADHESIVE PRODUCT APPROVALS |
| | SUBMITTED. CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED |
| | BY CITY POLICY FOR ALL ROOFING PERMITS TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "D". SEE |
| | STRUCTURAL DRAWING S-2. COORDINATE WITH DESIGNER OF |
| | RECORD TO AVOID CONFLICTS/DELAYS. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |
| | REMAINDER: |
| | THIS PROJECT WAS APPROVED WITH PROVISO. PLEASE PROVIDE |
| | ALL THE REQUIRED INFORMATION FOR REVIEW PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. SEE COPY OF |
| | PROVISO BELOW. |
| | |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ROOF TILE AND SPECIFY FASTENING. IF USING SCREWS, |
| | SPECIFY SIZE & NUMBER. |
| | B)ROOF TILE ADHESIVE IF SPECIFIED ABOVE. |
| | C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. NOTE: RAS |
| | 117 CALCULATIONS IF REQUIRED. |
| | D)ENTRY DOOR. |
| | E)LAUNDRY DOOR. |
| | F)SLIDING GLASS DOORS. |
| | G)FIXED WINDOWS. |
| | H)HORIZONTAL SLIDING WINDOWS. |
| | I)CASEMENT WINDOWS. |
| | I)OVERHEAD GARAGE DOOR. |
| | |