| Plan Review Notes For Permit 21040723 |
| Permit Number |
21040723 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-26 13:25:48 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FPC 918.8 PROHIBITED INSTALLATIONS - THE DETAIL | | | FOR THE TERMINATION (VENT) OF THE RISER FOR CONDENSATES | | | AND WATER HEATER DRAIN PANS IS A MODIFIED AIR | | | ADMITTANCE VALVE AND IS NOT ALLOWED TO BE INSIDE A | | | PLENUM. PLEASE RECONFIGURE AND CHOOSE ANOTHER LOCATION | | | FOR THE VENTING OF THE CONDENSATE/WATER HEATER PAN | | | DRAIN STACKS. | | | | | | 2. 2020 FPC 606.1 (4) - A FULL OPEN SHUT OFF IS | | | REQUIRED AT THE BASE OF EVERY WATER RISER PIPE. PLEASE | | | SHOW THE SHUT OFF ON THE WATER ISOMETRIC. | | | | | | 3. 2020 FPC 606.1 (6) - A FULL OPEN SHUT OFF VALVE IS | | | REQUIRED AT THE ENTRANCE TO EACH UNIT. PLEASE DETAIL | | | THIS IN THE UNIT TYPE ISOMETRICS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|