2022-04-26 13:25:482ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 918.8 PROHIBITED INSTALLATIONS - THE DETAIL
 FOR THE TERMINATION (VENT) OF THE RISER FOR CONDENSATES
 AND WATER HEATER DRAIN PANS IS A MODIFIED AIR
 ADMITTANCE VALVE AND IS NOT ALLOWED TO BE INSIDE A
 PLENUM. PLEASE RECONFIGURE AND CHOOSE ANOTHER LOCATION
 FOR THE VENTING OF THE CONDENSATE/WATER HEATER PAN
 DRAIN STACKS.
  
 2. 2020 FPC 606.1 (4) - A FULL OPEN SHUT OFF IS
 REQUIRED AT THE BASE OF EVERY WATER RISER PIPE. PLEASE
 SHOW THE SHUT OFF ON THE WATER ISOMETRIC.
  
 3. 2020 FPC 606.1 (6) - A FULL OPEN SHUT OFF VALVE IS
 REQUIRED AT THE ENTRANCE TO EACH UNIT. PLEASE DETAIL
 THIS IN THE UNIT TYPE ISOMETRICS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  