Plan Review Notes
Plan Review Notes For Permit 21040723
Permit Number 21040723
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-30 11:25:2509/30/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P2.1.1, THERE IS A 3-INCH DOMESTIC WATER
 LINE IN THE DOMESTIC PUMP ROOM OVER THE AC UNIT. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 2. ON SHEET 5.1.1;
  
 A. THERE ARE VENTS THROUGH THE ROOF FOR CONDENSATE AND
 RELIEF. I HAD A CONVERSATION WITH SOME ABOUT THE VENT
 THROUGH THE ROOF, AND THEIR CONCERN WAS PENETRATION. WE
 SPOKE ABOUT PUTTING THE VENTS WITH PERFORATED CAP IN
 THE AC CLOSET WITH 90, AND DUE TO THE PLENUM'S FLAME
 INDEX, IT WOULD NEED TO BE CONVERTED TO CPVC IN THE
 WALL. WOULD YOU PLEASE SHOW DETAIL AND CHANGE THE
 ISOMETRIC OR CLARIFY IF THE VENT IS BEING USED PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. ON THE STORM, A NEW FLOOR DRAIN IS ADDED ON THE
 SECOND FLOOR IN THE DOMESTIC PUMP ROOM THAT IS NOT
 SHOWN. WOULD YOU PLEASE ADD IT AND SIZE ALL HORIZONTAL
 AND VERTICAL PIPES AS ON P2.1.1 PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. ON SHEET 5.1.2;
  
 A. ON RISER FOUR, THERE IS A SECOND WATER CLOSET LABEL
 ON THE SECOND AND THIRD FLOORS. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON RISER TWO, THE LABEL SAYS SHOWERS, AND THE
 ARCHITECTURAL DRAWINGS SHOW TUBS. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. ON RISER FIVE, THE LAV WAS ADDED TO THE RISER AND
 NOT SHOWN. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 4. ON SHEET 5.1.3, VALVES ARE MISSING ON EACH RISER PER
 THE 2020 FBC SEC. 606.1 (4). WOULD YOU PLEASE SHOW
 ACCESS TO THESE VALVES PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 5. ON SHEET 5.1.4, THE RISER SIX WAS DELETED AS SHOWN
 ON P2.1.1, AND A DIFFERENT CONFIGURATION WAS USED BUT
 NOT SHOWN. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 6. ON SHEET 5.1.5;
  
 A. SHUTOFF VALVES FOR EACH UNIT ARE MISSING. WOULD YOU
 PLEASE ADD PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE PROVIDE THE PAGE NUMBER FOR THE EWH
 SCHEDULE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. ON UNIT TYPES B1 AND B2 SHOW A RECIRCULATING SYSTEM,
 AND ON P6.1.1 DETAIL ONE, THE WATER HEATER HAS THE
 RECIRCULATING PUMP NUMBER 8 BUT NO NUMBER CORRESPONDING
 TO THE SKETCH. IT MAY HAVE BEEN MISTAKEN WITH NUMBER 5.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. THERE IS A NEW COMMENT ADDED IN B1 FOR 1-INCH
 INSULATION ON THE FIRST EIGHT FEET. IF YOU ARE USING A
 RECIRCULATING SYSTEM, THE PIPING SHALL BE INSULATED IN
 ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING OF
 A CIRCULATING PER C404.4 (A) INSULATION OF PIPING.
  
 E. THE RECALCULATING PER MANUFACTURES SPECIFICATION AND
 MAINTENANCE MAY REQUIRE SHUTOFF VALVES ON EACH SIDE OF
 THE RECALCULATING PUMP AND PER THE 2020 FBC SEC. 606.2
 LOCATION OF SHUTOFF VALVES.
  
 F. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 IT IS NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT
 IN THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A
 TABLE THAT LIMITS THE BETWEEN THE SOURCE AND THE
 OUTLET; PLEASE REFER TO TABLE 405.5.1 FOR THE MAXIMUM
 ALLOWABLE PIPE LENGTH METHOD AND SIZE ACCORDANTLY.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  