| 2021-09-30 11:25:25 | 09/30/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P2.1.1, THERE IS A 3-INCH DOMESTIC WATER |
| | LINE IN THE DOMESTIC PUMP ROOM OVER THE AC UNIT. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 2. ON SHEET 5.1.1; |
| | |
| | A. THERE ARE VENTS THROUGH THE ROOF FOR CONDENSATE AND |
| | RELIEF. I HAD A CONVERSATION WITH SOME ABOUT THE VENT |
| | THROUGH THE ROOF, AND THEIR CONCERN WAS PENETRATION. WE |
| | SPOKE ABOUT PUTTING THE VENTS WITH PERFORATED CAP IN |
| | THE AC CLOSET WITH 90, AND DUE TO THE PLENUM'S FLAME |
| | INDEX, IT WOULD NEED TO BE CONVERTED TO CPVC IN THE |
| | WALL. WOULD YOU PLEASE SHOW DETAIL AND CHANGE THE |
| | ISOMETRIC OR CLARIFY IF THE VENT IS BEING USED PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. ON THE STORM, A NEW FLOOR DRAIN IS ADDED ON THE |
| | SECOND FLOOR IN THE DOMESTIC PUMP ROOM THAT IS NOT |
| | SHOWN. WOULD YOU PLEASE ADD IT AND SIZE ALL HORIZONTAL |
| | AND VERTICAL PIPES AS ON P2.1.1 PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. ON SHEET 5.1.2; |
| | |
| | A. ON RISER FOUR, THERE IS A SECOND WATER CLOSET LABEL |
| | ON THE SECOND AND THIRD FLOORS. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON RISER TWO, THE LABEL SAYS SHOWERS, AND THE |
| | ARCHITECTURAL DRAWINGS SHOW TUBS. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. ON RISER FIVE, THE LAV WAS ADDED TO THE RISER AND |
| | NOT SHOWN. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 4. ON SHEET 5.1.3, VALVES ARE MISSING ON EACH RISER PER |
| | THE 2020 FBC SEC. 606.1 (4). WOULD YOU PLEASE SHOW |
| | ACCESS TO THESE VALVES PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 5. ON SHEET 5.1.4, THE RISER SIX WAS DELETED AS SHOWN |
| | ON P2.1.1, AND A DIFFERENT CONFIGURATION WAS USED BUT |
| | NOT SHOWN. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 6. ON SHEET 5.1.5; |
| | |
| | A. SHUTOFF VALVES FOR EACH UNIT ARE MISSING. WOULD YOU |
| | PLEASE ADD PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. WOULD YOU PLEASE PROVIDE THE PAGE NUMBER FOR THE EWH |
| | SCHEDULE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. ON UNIT TYPES B1 AND B2 SHOW A RECIRCULATING SYSTEM, |
| | AND ON P6.1.1 DETAIL ONE, THE WATER HEATER HAS THE |
| | RECIRCULATING PUMP NUMBER 8 BUT NO NUMBER CORRESPONDING |
| | TO THE SKETCH. IT MAY HAVE BEEN MISTAKEN WITH NUMBER 5. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. THERE IS A NEW COMMENT ADDED IN B1 FOR 1-INCH |
| | INSULATION ON THE FIRST EIGHT FEET. IF YOU ARE USING A |
| | RECIRCULATING SYSTEM, THE PIPING SHALL BE INSULATED IN |
| | ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING OF |
| | A CIRCULATING PER C404.4 (A) INSULATION OF PIPING. |
| | |
| | E. THE RECALCULATING PER MANUFACTURES SPECIFICATION AND |
| | MAINTENANCE MAY REQUIRE SHUTOFF VALVES ON EACH SIDE OF |
| | THE RECALCULATING PUMP AND PER THE 2020 FBC SEC. 606.2 |
| | LOCATION OF SHUTOFF VALVES. |
| | |
| | F. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM |
| | IT IS NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT |
| | IN THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A |
| | TABLE THAT LIMITS THE BETWEEN THE SOURCE AND THE |
| | OUTLET; PLEASE REFER TO TABLE 405.5.1 FOR THE MAXIMUM |
| | ALLOWABLE PIPE LENGTH METHOD AND SIZE ACCORDANTLY. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |