| Plan Review Notes For Permit 21040677 |
| Permit Number |
21040677 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-27 05:53:31 | 1) THE PLANS REFER TO THE THE 2017 FBC. THE PLANS SHALL | | | BE DESIGNED UNDER THE 2020 FBC WWHICH WENT INTO EFFECT | | | DECEMBER 31, 2020. REVISE THE NOTE ON ALL AFFECTED | | | SHEETS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER | | | HEATER DETAIL ON SHT. P-1.01. | | | 3) SHT. P-1.01 - THE SOIL STACK FOR THE SECOND FLOOR | | | BATH #2 SHALL NOT CONNECT TO THE FIRST FLOOR BRANCH | | | DRAIN BETWEEN THE WATER CLOSET AND THE | | | LAVATORY.FBC-PLUMBING SEC. 912.1. | | | 4) SHT. C-1 - WHERE ARE THE AREA DRAINS DISCHARGING? | | | THE DISCHARGE SHALL CCOMPLY WITH FBC-PLUMBING | | | SEC.1101.2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|