Plan Review Notes
Plan Review Notes For Permit 21040677
Permit Number 21040677
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-27 05:53:311) THE PLANS REFER TO THE THE 2017 FBC. THE PLANS SHALL
 BE DESIGNED UNDER THE 2020 FBC WWHICH WENT INTO EFFECT
 DECEMBER 31, 2020. REVISE THE NOTE ON ALL AFFECTED
 SHEETS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER
 HEATER DETAIL ON SHT. P-1.01.
 3) SHT. P-1.01 - THE SOIL STACK FOR THE SECOND FLOOR
 BATH #2 SHALL NOT CONNECT TO THE FIRST FLOOR BRANCH
 DRAIN BETWEEN THE WATER CLOSET AND THE
 LAVATORY.FBC-PLUMBING SEC. 912.1.
 4) SHT. C-1 - WHERE ARE THE AREA DRAINS DISCHARGING?
 THE DISCHARGE SHALL CCOMPLY WITH FBC-PLUMBING
 SEC.1101.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  