2021-04-27 06:36:521) SHT. P-1.02 - NOTE #7 REFERS TO THE TRACER WIRE
 BEING HELD TO THE TOP OF THE GAS PIPE. THE TRACER WIRE
 IS NOT PERMITTED TO TOUCH THE PE PIPE PER FBC-FUEL GAS
 SEC.404.17.3.
 2) ALL GAS EQQUIPMENT SHALL BE LISTED AND LABELED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT BEING INSTALLED AT THIS TIME. FBC-FUEL GAS
 SEC.301.3.
 3) THE GAS DRYER MAKEUP AIR SHALL COMPLY WITH FBC-FUEL
 GAS SEC.614.6.
 4) THE TANKLESS WATER HEATERS HALL BE INSTALLED A
 MINIMUM OF 4 FEET FROM ANY OPERABLE DOOR OR WINDOW PER
 THE MANUFACTURER'S INSTALLATION MANUAL. THE DISTANCE TO
 SOFFIT VENNTS SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION MANUAL.
 5) THE 1 1/4 INCH SCH. 40 PIPE ON THE LOW PRESURE
 SYSTEM IS UNDERSIZED. A MAXIMUM OF 322,000 BTU'S SHALL
 BE SUPPLIED BY A 1- 1/4 INCH SCH. 40 METALLIC PIPE PER
 FBC-FUEL GAS TABLE 402.4 (2) AT 143 FEET LENGTH.
 6) THE CSST SECTIONS OF PIPE ARE UNDERSIZED. A MXXIMUM
 OF 320,000 BTU'S SHALL BE SUPPLIED BY A CSST LINE WITH
 AN EHD OF 46 AT A DEVELOPED LENGTH OF 143 FEET PER
 FBC-FUEL GAS TABLE 402.4.(15).
 7) THE 3/4- INCH SCH. 40 LINE LINE TO THE RANGE IS
 UNDERSIZED . THE MINIMUM SIZE LINE SHALL COMPLY WITH
 FBC-FUEL GAS TABLE 402.4 (2).
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE GAS SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692