| 2021-04-26 09:49:24 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| | |
| | 1) SHEET E101 ELECTRICAL PLAN: ELECTRICAL NOTE NO. 6. |
| | REFERENCES TO CODES ARE OUTDATED. PLEASE SEE BELOW FOR |
| | CURRENT CODES AND UPDATE NOTE TO REFLECT THEM. |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | 1) SHEET E-2.01 ELECTRICAL PLAN: ELECTRICAL NOTE 5. |
| | CURRENT FLORIDA ENERGY CODE 2020 7TH EDITION REQUIRES |
| | THAT: |
| | |
| | "R 404.1 NOT LESS THAN 90 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN EFFICACY |
| | OF AT LEAST 45 LUMENS-PER-WATT OR SHALL UTILIZE LAMPS |
| | WITH AN EFFICACY OF NOT LESS THAN 65 LUMENS-PER-WATT." |
| | |
| | PLEASE UPDATE NOTE TO REFLECT NEW CODE REQUIREMENTS |
| | |
| | 2) SHEET E-2.01 ELECTRICAL PLAN (FEEDER SIZES): FEEDER |
| | NO. 2 (3#2/0, 1#4 CU) IS TOO SMALL. PLEASE INCREASE TO |
| | NEXT SIZE (#3/0 CU) MINIMUM. NEC 240.4(B)(2) |
| | |
| | 3) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CURRENT AT |
| | SERVICE EQUIPMENT AND PANELS. FBC 107 |
| | |
| | 4) A MINIMUM OF ONE COMMUNICATION OUTLET SHALL BE |
| | INSTALLED AS PER NEC 800.156 (A NOTE WILL SUFFICE) |
| | |
| | 5) SHEET E-2.01 ELECTRICAL PLAN: ELECTRICAL NOTES MAKE |
| | REFERENCES TO NEC 2014 AND FBC 2014. PLEASE UPDATE CODE |
| | REFERENCES ON ALL DRAWINGS AND NOTES TO REFLECT NEW |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | 6) FUTURE GENERATOR WILL REQUIRE SEPARATE PERMIT FBC |
| | 107. |
| | |
| | |