| Date |
Text |
| 2021-06-23 17:18:35 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 2ND BUILDING REVIEW DENIED: |
| | |
| | 1) OK |
| | 2A-D) OK |
| | 3A-3G) OK |
| | |
| | 3H) DENIED; SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 |
| | ACCESS. CODE. SPOUT OUTLETS SHALL |
| | COMPLY WITH: 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR |
| | OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. 602.7 SPOUT |
| | HEIGHT FOR THE |
| | STANDING PERSONS SHALL BE BETWEEN 38 TO 43 INCHES ABOVE |
| | FINISH FLOOR. |
| | 6/23/21 DESIGN PROFESSIONAL'S RESPONS IS ACKNOWLEDGED. |
| | HOWEVER, AS PER FBC P 403.5, PLEASE INDICATE ON PLANS |
| | THAT THE MOST REMOTE LOCATION WITHIN THE TENANT SPACE |
| | IS NO MORE THAN 300' FROM A DRINKING FOUNTAIN ALONG AN |
| | ACCESSIBLE ROUTE. |
| | |
| | 4) OK, DEFERRED SUBMITTAL AND SEPARATE PERMIT IS |
| | REQUIRED FOR AWNING & CANOPIES. |
| | |
| | 5) DENIED: SUBMIT PRODUCT APPROVALS FOR, COMPONENTS AND |
| | CLADDING. |
| | THE DEMO SHEET NOTES 11 & 12 BOTH INDICATE THE REMOVAL |
| | OF STOREFRONT |
| | WINDOW AND DOOR SYSTEMS. SHEET A-550 SHOW ELEVATIONS OF |
| | THE NEW |
| | STOREFRONT SYSTEMS. SHEET S-200 SHOWS THE NEW |
| | STRUCTURAL STEEL FOR THE |
| | STOREFRONT SYSTEM AS WELL AS THE NEW STRUCTURAL STUDS |
| | FOR THE BLOCKED IN AREA |
| | OF STOREFRONT. COMPONENTS & CLADDING. 2020 FBC-B |
| | 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF |
| | COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS, MULLIONS. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, EFIS |
| | SYSTEMS, (D) ROOFING PRODUCTS |
| | AND ASSEMBLIES, ROOF TOP CURBS FOR RTU UNITS, |
| | LIGHTWEIGHT CONCRETE INSULATION, |
| | ROOF TOP VENTILATORS. |
| | 6/23/21, PLEASE PROVIDE ALL PRODUCT APPROVALS(WITH |
| | DESIGNER OF RECORD'S APPROVED REVIEW STAMPS) FOR ALL OF |
| | THE ABOVE NOTED ITEMS. |
| | |
| | 6) DENIED; IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY |
| | ON THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO |
| | THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, |
| | LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES |
| | FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | 6/23/21 PLEASE INDICATE, WITHIN THE SUBMITTED SHOP |
| | DRAWIMGS, THE SYSTEMS AND OPTIONS FOR STOREFRONT SYSTEM |
| | THAT WILL BE USED. |
| | |
| | 7) DENIED; W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH |
| | ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE 61G20 |
| | SHALL BE REVIEWED |
| | AND APPROVED IN WRITING (SHOP DRAWING STAMP OF |
| | APPROVAL) BY THE DESIGNER |
| | OF RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL |
| | APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, |
| | REPORTS, SHOP DRAWINGS ETC. |
| | 6/23/2021 PLEASE PROVIDE ALL SHOP DRAWINGS AND PRODUCT |
| | APPROVALS, INCLUDING THOSE THAT HAVE ALREADY BEEN |
| | SUBMITTED, WITH DESIGNER OF RECORD'S APPROVED REVIEW |
| | STAMP. |
| | |
| | 8) OK, DEFERRED SUBMITTAL REQUIREMENT HAS BEEN |
| | ACKNOWLEDGED BY DESIGN PROFESSIONAL. |
| | |
| | 9) OK |
| | |
| | 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE |
| | YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | |
| | |