Plan Review Notes
Plan Review Notes For Permit 21040663
Permit Number 21040663
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-29 06:46:311) SHT. LS 01 NOTES THE OCCUPANCY OF SPACE B03 AS AN
 "M" OCCUPANCY (MERCANTILE). THIS SPACE IS GOING TO BE A
 BEAUTY SHOP/NAIL SALON WHICH IS CLASSIFIED AS A GROUP
 "B" OCCUPANCY ACCORDING TO FBC-BUILDING SEC. 304.1. HOW
 CAN THIS BE CLASSIFIED AS AN "M" OCCUPANCY? IS THIS
 BUILDOUT A CHANGE OF OCCUPANCY/CHANGE OF USE? INDICATE
 ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 2) INDICATE THE PREVIOUS OCCUPANCY OF ALL THE SPACES ON
 THIS PLAN AND INDICATE ON THE PLANS IF ANY OF THIS NEW
 WORK WILL BE A CHANGE OF OCUPANCY/CHANGE OF USE. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) THE BREAKROOM SINK (NOT THE MOP SINK) IN THE
 EMPLOYEE BREAK AREA IN TENANT SPACE B03 SHALL COMPLY
 WITH THE FBC-ACCESS. SECS. 606.2, 606.3, 606.4, 606.5.
 4) THE SINK IN ONE OF THE WAX ROOMS IN TENANT SPACE B03
 SHALL COMPLY WITH FBC-ACCESS. SECS. 606.2, 606.3,
 606.4, 606.5.
 5) THE WALL FINISH AROUND THE MOP SINK SHALL OMPLY WITH
 FBC-BUILDING SEC.1210.2.2.
 6) SHT. A631- DETAIL #1 - THE DOOR CANNOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY OR THE WATER
 CLOSET PER FBC SEC. 603.2.3 UNLESS A 30 INCH WIDE
 MINIMUM BY 48 INCH LONG MINIMUM CLEAR FLOOR SPACE IS
 PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR
 SWING. SHOW THE REQUIRED CCLEAR FLOOR SPACE OR REVERSE
 THE DOOR SWING.
 7) SHT. A631 - THE HEIGHT OF THE GRAB BARS ARE SHOWN
 MEASURED TO THE CENTERLINE OF THE GRAB BARS. GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 PER FBC-ACCESS. SEC. 609.4.
 8) SHT. A631 - TOILET ACCESSORY MOUNTING HEIGHTS - THE
 OUTLET OF THE SOAP DISPENSER SHALL BE LOCATED A MAXIMUM
 OF 48 INCHES ABOVE THE FINISH FLOOR. FBC-ACCESS.
 SECS.308.2, 308.3.
 9) SHT. A631 - ELEVATION #2 - THE LAVATORY SHALL BE
 LOCATED A MINIMUM OF 15 INCHES FROM THE WALL TO THE
 CENTERLINE OF THE LAVATORY PER FBC-PLUMBING
 SEC.405.3.1.THE PLANS SHOW THE LAVATORY AT 14 INCHES.
 11) SINCE THIS IS A BUSINESS OCUPANCY A MINIMUM OF 2
 DRINKING FOUNTAINS ARE REQUIRED PER FBC- PLUMBING TABLE
 403.1 AND SEC.410.3.
 12) SHT. P001 - NOTE #13 REFERS TO FIRE RATED FOAM,
 CAULKING OR PUTTY FOR SEALING PENETRATIONS THROUGH
 RATED WALLS. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THESE PRODUCTS TO ONIRM COMPATABILITY ITH THE
 PENETRATING ITEM. WPB AMEND. TO FBC SEC. 107.2.1.
 13) SHT. P001 - WATER PIPE SIZING TABLE NOTE REFERS TO
 CHAPTER 4 OF MIAMI-DADE ORDINANCE 08-14. THIS NOTE IS
 NOT APPLICABLE. REMOVE THIS NOTE FROM THE PLANS.
 14) SHT. P001 - WATER PIPE SIZING TABLE NOTE #2 REFERS
 TO FBC SECS. 2318.1.15 AND 2517.5.1.1.REMOVE THIS NOTE
 FROM THE PLANS AS BOTH SECTIONS ARE SHOWN AS "RESERVED"
 IN THE CODE AND NOT APPLICAABLE.
 15) SHT. P001 - SHOW THE PAN DRAIN FOR THE WATER HEATER
 AND THE TERMINATION POINT OF THE PAN DRAIN ON THE WATER
 HEATER DETAIL.SHOW THE SIZE OF THE PAN DRAIN.
 16) PROVIDE DETAILS OF THE SHELF CONSTRUCTION FOR THE
 WATER HEATER. THE WATER HEATER WILL WEIGH MORE THAN 665
 POUNDS WHEN FILLED WITH WATER. THERE IS NO INFORMATION
 ON THE PLANS AS TO HOW THIS SHELF IS TO BE CONSTRUCTED
 OR ANY INFORMATION ON LOAD BEARING STRENGTH,
 CONNECTIONS, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 17) SHT. P001 SHOWS A PRESSURE RELIEF VALVE ON THE COLD
 WATER INLET TO THE WATER HEATER. CLARIFY.
 18) THE ENTIRE HOT WATER PIPING SYSTEM SHALL BE
 INSULATED WITH INSULATION WITH A WALL THICKNESS IN
 ACCORDANCE WITH FBC-ENERGY SEC.C404.4 AND TABLE
 C403..2.10. SHOW COMPLIANCE ON THE PLANS.
 19) A BACKFLOW PREVENTER WILL BE REQUIRED ON THE WATER
 LINE TO THE TOWEL STEAMER.FBC-PLUMBING SEC.608.3.
 20) HEATED WATER SUPPLY PIPING SHALL BE IN ACORDANCE
 WITH SECTION C404.5.1 OR C404.5.2. SHOW COMPLIANCE ON
 THE WATER RISER.
 21) PROVISIONS SHALL BE MADE FOR THERMAL EXPANSION OF
 THE WATER SSUPPLY SYSTEM. IF THE PRESSURE RELIEF VALVE
 ON THE COLD WATER SYTEM IS TO MEET THIS PROVISION,
 LABEL THE VALVE AS A THERMAL EXXPAANSION VALVE AND
 SHOWW THE TERMINATION POINT OF THE DISCHARGE LINE OF
 THE VALVE.
 22) THE WATER CONNECTION TOWEL STEAMER IS NOT SHOWN ON
 THE WATER RISER. CLARIFY.
 23) SUBMIT A CONCRETE SLAB DETAIL SHOWING HOW THE SLAB
 CUTOUT WILL BE REPAIRED TO MAINTAIN THE STRUCTURAL
 INTEGRITY. INDICATE THE SIZE OF REINFORCING BARS TO BE
 USED, THE EMBEDMENT DEPTH THAT THE REBAR WILL BE
 DOWELED INTO THE EXISTING SLAB, HOW THE DOWELS WILL BE
 SET IN THE EXISTING SLAB, AND THE SPACING ON CENTER OF
 THE DOWELS. SHOW THE THICKNESS OF THE EXISTING SLAB &
 THE REPAIR. A VAPOR BARRIER AND TERMITE POISONING IS
 REQUIRED.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 24) THE WATER SUPPLY TO THE PEDICURE CHAIRS SHALL BE
 TEMPERED WATER PER FBC-PLUMBING SEC. 412.5. THE
 TEMPERED WATER VALVE SHALL COMPLY WITH ASSE 1070.
 25) SHT. LS 01- SPACE B03 IS LABELED AS B03 BUT THE
 SAME SPACE IS LABELED AS B01 ON SHT.P101. CLARIFY.
 26) SHT. A101 - IDENTIFY EACH BAY ON THE FLOOR PLAN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 27) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE PEDICURE CHAIRS.WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  