2021-05-11 11:26:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21040663
 ADD: 1885 PALM BEACH LAKES BLVD. # B1, B3 & B4
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 11TH, 2021
 ACTION: DENIED
 1) BOTH THE PERMIT APPLICATION AND THE SET OF PLANS
 INDICATE WORK TO BE ACCOMPLISHED IN B01, B03 & B04
 UNITS. THE SUITES HAVE HAD TENANT ADDRESSES ASSIGNED TO
 THEM, PLEASE USE THESE ADDRESSES FOR FUTURE REFERENCES
 ON THE PLANS.
 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
 CITY MUNI CODE SEC.78-6 (1-7) (2) LOCATION, BUILDINGS
 CONTAINING MORE THAN ONE ADDRESS. ALL ADDRESSES SHALL
 BE POSTED ON THAT PORTION OF THE STRUCTURE FRONTING OR
 FACING UPON THE STREET OR PRINCIPAL VEHICULAR ACCESS TO
 THE PREMISES, SO AS TO BE READILY VISIBLE TO
 APPROACHING VEHICLES. THE PLACEMENT OF NUMBERS ON
 BUILDINGS OR FENCES, AS THE CASE MAY BE, SHALL BE
 SUBJECT TO THE DIRECTION OR APPROVAL OF THE CITY'S
 CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS WHICH
 CONTAIN MORE THAN ONE COMMERCIAL, INDUSTRIAL, OR
 INSTITUTIONAL ADDRESS SHALL POST A SEPARATE ADDRESS
 MEETING THE REQUIREMENTS OF THIS SECTION AT THE
 EXTERIOR ENTRANCE TO EACH INDIVIDUAL ADDRESS OR COMMON
 EXTERIOR ENTRANCE TO SEVERAL ADDRESSES THEREIN, AND THE
 UNIT NUMBER SHALL ALSO BE POSTED ON THE EXTERIOR DOOR
 OF EACH UNIT SERVED BY SUCH A COMMON EXTERIOR ENTRANCE.
  
 2) LS01- LIFE SAFETY PLAN:
  
 2A) IT IS A BIT CONFUSING, THIS SHEET IS LISTED AS THE
 LIFE SAFETY SHEET, 3 SEPARATE TENANT BAYS ARE SHOWN BUT
 ONLY THE B-3 BAY IS ACTUALLY A LIFE SAFETY PLAN. THE
 UPPER LEFT HAND CORNER OF THE SHEET THE HEADING IS FOR
 TENANT B01. IS THIS SHEET FOR ALL 3 TENANTS OR FOR
 TENANT B01? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2B) THE LIFE SAFETY PLAN STATES THE OCCUPANCY TYPE IS
 MERCANTILE. FURTHER DOWN THE OCCUPANCY TYPE IS DECLARED
 FOR ALL 3 TENANT SPACES, B1- N/A, BOTH B03 AND B04 AS
 MERCANTILE. PLEASE SEE SECTION 304.1 IN THE 2020
 FBC-BUILDING CODE. BOTH BARBER AND BEAUTY SHOPS ARE
 CLASSIFIED AS BUSINESS OCCUPANCIES. PLEASE UPDATE THE
 PLAN. SINCE TENANT SPACE B-01IS UNDECLARED OCCUPANCY /
 SHELL SPACE WOULDN?T B04 NOW DO THE SAME SINCE THERE IS
 NO TENANT FIT UP AS PART OF THIS PERMIT AND NOT A
 DECLARED OCCUPANCY TYPE?
  
 2C) THE DEMOLITION PLAN DOES NOT DECLARE WHAT TYPE OF
 OCCUPANCY B3 WAS? MOST LIKELY IT WAS A MERCANTILE
 OCCUPANCY AND IF SO THEN THE BEAUTY SHOP MOVING INTO
 THE NEW TENANT SPACE B03 WOULD BE A CHANGE IN OCCUPANCY
 AND THE PLANS WOULD NEED TO SHOW COMPLIANCE WITH THE
 2020 FBC-EXISTING BUILDING CODE( NOT LISTED UNDER
 APPLICABLE CODES) AND SECTION 1001.2.2.1 BUILDINGS
 UNDERGOING A PARTIAL CHANGE OF OCCUPANCY.
  
 2D) PLEASE ALSO NOTE A CHANGE IN THE 2020 FBC-BUILDING
 FOR BUSINESS OCCUPANCIES SEE TABLE 1004.5. THE
 OCCUPANCY LOAD FACTOR IS NO LONGER 100 SQ. FT. BUT NOW
 150 SQ. FT. OCCUPANT LOAD FACTOR.
  
 3) SHEET A631 ENLARGED RESTROOM:
  
 3A) THE WATER CLOSET GRAB BARS ARE DIMENSIONED FROM
 FLOOR TO THE CENTERLINE OF THE BAR. 2020
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 3B) THE TOILET PAPER DISPENSER IS NOT DIMENSIONED FROM
 THE WATER CLOSET. TOILET PAPER DISPENSERS. 604.7. THE
 TOILET PAPER DISPENSER SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 3C) THE MIRROR IS DIMENSIONED TO THE BOTTOM OF THE
 MIRROR FRAME NOT THE REFLECTIVE SURFACE. 603.3 MIRRORS.
 2020 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 3D) TOILET ROOM DOORS. 2017 FBC-ACCESSIBILITY CODE
 FIGURE 604.8.1.6 SHOWS AN OUTSWING DOOR. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 PLEASE SEE EXCEPTION 2. WHERE TOILET ROOMS ARE FOR
 INDIVIDUAL USE AND A CLEAR FLOORS SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING. WHAT IS MISSING IS THE REQUIRED 30X48 INCH
 CLEAR FLOOR SPACE BEYOND THE ARC OF THE DOOR. USUALLY
 AT A 45% ANGLE TO THE DOOR ENTRANCE.
  
 3E) SHEET A101 DOES NOT INDICATE A HIGH LOW WATER
 FOUNTAIN. DRINKING FOUNTAINS. 2020 FBC-ACCESSIBILITY
 CODE. 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 3F) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 3G) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 3H) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 4) SHEET A320 DETAILS 1 & 2 SHOW AWNING/ CANOPIES.
 AWNING AND CANOPY INSTALLATIONS REQUIRE A SEPARATE
 PERMIT, REVIEW AND ASSOCIATED FEES, 105.1 PERMITS.
  
 5) SUBMIT PRODUCT APPROVALS FOR, COMPONENTS AND
 CLADDING. THE DEMO SHEET NOTES 11 & 12 BOTH INDICATE
 THE REMOVAL OF STOREFRONT WINDOW AND DOOR SYSTEMS.
 SHEET A-550 SHOW ELEVATIONS OF THE NEW STOREFRONT
 SYSTEMS. SHEET S-200 SHOWS THE NEW STRUCTURAL STEEL FOR
 THE STOREFRONT SYSTEM AS WELL AS THE NEW STRUCTURAL
 STUDS FOR THE BLOCKED IN AREA OF STOREFRONT.
 COMPONENTS & CLADDING. 2020 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS FOR
 RTU UNITS, LIGHTWEIGHT CONCRETE INSULATION, ROOF TOP
 VENTILATORS
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS
 EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT 561-805-6666.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  