| Plan Review Notes For Permit 21040661 |
| Permit Number |
21040661 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-25 17:09:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | #1 IS ONLY ALLOWED TO HAVE A 110A CIRCUIT BREAKER OR | | | FUSE INSTALLED, WIRE MUST BE A 1/0. 310.15(B)(16) |
|