2022-01-13 09:19:45NFIP PEER REVIEW STATUS IS DENIED.
 THE FOLLOWING CORRECTIONS ARE REQUIRED.
  
 1) A1. THE CURRENT OWNERS NAME IS 3010 FLAGLER LLC.
 2) A2. THE ZIP CODE IS 33407.
 3) A5. THE NEGATIVE SIGN AND W ARE BOTH GIVEN FOR
 LONGITUDE. SINCE YOU USED THE DIRECTION N FOR THE
 LATITUDE TO BE CONSISTANT USE W FOR LONGITUDE AND
 REMOVE THE NEGATIVE SIGN.
 4) A9. THE LOCATIONS, SIZE AND TYPE OF FLOOD VENTS NEED
 TO BE SHOWN ON THE FLOOR PLANS.
 5) A9(C). IF YOU ARE USING THE ENGINEERED SMART VENTS
 WHICH MEASURE 15-3/4" X 7-3/4", THEN EACH OPENING IS
 122.1 SQUARE INCHES. THE TOTAL FOR SIX IS 732.6 SQUARE
 INCHES. FEMA'S ELEVATION CERTIFICATE INSTRUCTIONS
 ALLOWS THIS WHEN THE NET AREA OF THE FLOOD VENTS CAN
 NOT BE REASONABLY ESTIMATED. THE TYPE OF VENT AND
 COVERAGE CAN BE INDICATED IN THE COMMENT SECTION.
 6) C2. THE BENCH MARK UTILIZED SHOULD BE THE PID OR
 OTHER UNIQUE IDENTIFIER ASSIGNED BY THE MAINTAINER OF
 THE BENCHMARK. THE VERTICAL SHOULD BE NAVD 88.
 7) C2(E) THE ELEVATIONS OF THE GENERATOR AND A/C PADS
 NEED TO BE SHOWN ON THE CONSTRUCTION DRAWINGS.
 8) C2(F) & (G) THE LOWEST ADJACENT GRADE APPEARS TO BE
 5.92 FT AT THE ATTACHED GARAGE AND THE HIGHEST ADJACENT
 GRADE APPEARS TO BE 7.5 FT. AT THE FRONT OF THE
 RESIDENCE.
 9) IN SECTION D MARK YES OR NO TO THE QUESTION OF
 WHETHER OR NOT LAT. AND LONG. WERE PROVIDED BY A
 LICENSED LAND SURVEYOR.
 10) NOTES SHOULD BE ADDED TO THE PLANS FOR THE GARAGE
 TO SPECIFY THAT ALL MATERIALS INSTALLED BELOW THE
 DESIGN FLOOD ELEVATION SHALL BE FLOOD DAMAGE RESISTANT
 AND ALL EQUIPMENT IS TO BE ELEVATED ABOVE THE DFE.