| 2021-06-28 12:50:41 | PLAN REVIEW / NFIP |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: |
| | |
| | PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| | (SFHA). IT IS LOCATED IN ZONE AE WITH BASE FLOOD |
| | ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. DESIGN FLOOD |
| | ELEVATION SHALL BE 9.0 FEET NAVD. |
| | |
| | 1. PROVIDE A CONSTRUCTION DRAWING ELEVATION CERTIFICATE |
| | (EC) |
| | |
| | THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| | (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS |
| | AE WITH BASE FLOOD ELEVATIONS (BFE) OF 6.0 FEET AND 7.0 |
| | FEET NAVD. THE CITY OF WEST PALM BEACH (THROUGH CITY |
| | ORDINANCE NO. 4729-17) REQUIRES AN ADDITIONAL 24 INCHES |
| | OF FREEBOARD REQUIRING THE DESIGN FLOOD ELEVATION (DFE) |
| | TO BE 9. 0 FEET NAVD. PLEASE NOTE THIS INFORMATION ON |
| | YOUR PLANS. |
| | |
| | NOTICE: |
| | |
| | 3 EC S REQUIRED |
| | |
| | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| | REQUIRED AT TIME OF PERMIT APPLICATION. |
| | |
| | A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AT PLACEMENT OF 1ST FLOOR. |
| | |
| | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL |
| | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE |
| | BUILDING. |
| | |
| | 2. INDICATE THE FINISHED FLOOR ELEVATIONS OF THE MAIN |
| | RESIDENCE AND GARAGE ON THE FLOOR THE PLAN AND/OR |
| | FOUNDATIUON PLAN. |
| | R322.2.1ELEVATION REQUIREMENTS. |
| | |
| | 3. FLOOD OPENINGS: |
| | |
| | 1) PROVIDE FLOOD OPENINGS DESIGNED BY A DESIGN |
| | PROFESSIONAL PER R322.2.2 ENCLOSED AREA BELOW DESIGN |
| | FLOOD ELEVATION. |
| | 2) SIGNATURE AND SEAL OF DESIGNER IS REQUIRED. |
| | |
| | ENGINEERED FLOOD VENTS: |
| | |
| | 1) PROVIDE ENGINEERED FLOOD VENTS. (SMART VENTS) |
| | 2) ATTACH A COPY OF THE INDIVIDUAL ENGINEERED FLOOD |
| | VENT CERTIFICATION OR EVALUATION SERVICE REPORT ISSUED |
| | BY THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE |
| | (ICC ES). |
| | 3) PROVIDE FLORIDA PRODUCT APPROVALS OR MIAMI DADE |
| | NOA?S FOR PROPOSED SMART VENTS. |
| | 4) FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | 5) FLOOD OPENINGS SHALL BE INSTALLED PER |
| | R322.2.2.1INSTALLATION OF OPENINGS. |
| | 6) SHOW NUMBER AND LOCATION OF FLOOD OPENINGS ON |
| | FOUNDATION PLAN. |
| | |
| | FBC R322.2.2.1INSTALLATION OF OPENINGS. |
| | THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS |
| | INSTALLED SUCH THAT: |
| | 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON |
| | DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING |
| | HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD |
| | ELEVATION, EACH AREA SHALL HAVE OPENINGS. |
| | 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN |
| | 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR |
| | GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE |
| | IMMEDIATELY UNDER EACH OPENING. |
| | 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN |
| | DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED |
| | OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION |
| | |
| | NOTICE: EC PROVISO'S ON PLAN PAGES A1.0 AND A1.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |