| 2021-06-28 12:31:17 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. REF. COVER PAGE FOR THE FOLLOWING COMMENT: |
| | GOVERNING CODES ARE THE FBC 2020 7TH ED WITH 2017 NEC. |
| | |
| | 2. PROVIDE A BOUNDARY LINE SURVEY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 3. PROVIDE FINISHED FLOOR ELEVATION OF MAIN RESIDENCE |
| | AND GARAGE ON FLOOR PLAN AND/OR FOUNDATION PLAN. |
| | R322.2.1ELEVATION REQUIREMENTS. |
| | |
| | 4. IDENTIFY LOCATION OF REQUIRED FLOOD OPENINGS ON |
| | GARAGE FOUNDATION PLANS. SEE COMMENTS UNDER NFIP |
| | REVIEW. |
| | R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION. |
| | |
| | 5. PROVIDE A SITE DRAINAGE PLAN. DRAINAGE PERMIT |
| | 21030567 HAS NOT BEEN REVIEWED OR APPROVED. NO FEES |
| | PAID TO DATE. |
| | FBC R401.3 SITE DRAINAGE |
| | PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH |
| | FBC R401.3 DRAINAGE. |
| | |
| | 6. PROVIDE A SOILS REPORT. |
| | FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL |
| | BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND |
| | REPORTED IN ACCORDANCE WITH SECTION 1803.6. |
| | |
| | 7. REF. THE WINDOW AND DOOR SCHEDULE FOR THE FOLLOWING |
| | COMMENT: |
| | 7A) PROVIDE DESIGN PRESSURES FOR EACH OPENING. |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | 8. PRODUCT APPROVALS: |
| | 8A) FL15438-R2 HAS EXPIRED. PROVIDE PRODUCT APPROVAL |
| | APPROVED UNDER THE 2020 FBC 7TH ED. |
| | 8B) DESIGNER SHALL SELECT MODEL OF DOOR TO BE INSTALLED |
| | FROM FL15446-R2. |
| | 8C) PROVIDE INSTALLATION INSTRUCTIONS FOR FL15446-1. |
| | 8D) WINDOW SCHEDULE INDICATES SINGLE HUNG WINOWS SHALL |
| | BE INSTALLED. PROVIDE PRODUCT APPROVALS FOR SH WINDOWS. |
| | 8E) PROVIDE PRODUCT APPROVALS FOR 6" AND 10" HOLLOW |
| | CORE PLANKS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |