2021-06-01 07:28:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) NEED TO SHOW LOCATION OF PEDESTAL, IF ON DOCK THEN
 GFCI IS REQUIRED TO THE PEDESTAL. 555.3
  
 555.3 GROUND-FAULT PROTECTION. THE OVERCURRENT
 PROTECTIVE DEVICES THAT SUPPLY THE MARINA, BOATYARDS,
 AND COMMERCIAL AND NONCOMMERCIAL DOCKING FACILITIES
 SHALL HAVE GROUND-FAULT PROTECTION NOT EXCEEDING 30 MA.
  
 2) NEED TO SUBMIT CUTSHEET FOR PEDESTAL. 110.3
  
 3) THE USE OF EXPANSION FITTINGS WILL BE REQUIRED.