| Plan Review Notes For Permit 21040592 |
| Permit Number |
21040592 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-01 07:28:54 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) NEED TO SHOW LOCATION OF PEDESTAL, IF ON DOCK THEN | | | GFCI IS REQUIRED TO THE PEDESTAL. 555.3 | | | | | | 555.3 GROUND-FAULT PROTECTION. THE OVERCURRENT | | | PROTECTIVE DEVICES THAT SUPPLY THE MARINA, BOATYARDS, | | | AND COMMERCIAL AND NONCOMMERCIAL DOCKING FACILITIES | | | SHALL HAVE GROUND-FAULT PROTECTION NOT EXCEEDING 30 MA. | | | | | | 2) NEED TO SUBMIT CUTSHEET FOR PEDESTAL. 110.3 | | | | | | 3) THE USE OF EXPANSION FITTINGS WILL BE REQUIRED. | | | 352.44 | | | | | | |
|