| Plan Review Notes For Permit 21040592 |
| Permit Number |
21040592 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-29 12:27:06 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED TO SHOW WHERE MAIN IS TO SUBPANEL AND SEE IF IT | | | COMPLIES WITH 555.3 | | | | | | ELECTRICAL CONNECTION SHALL COMPLY WITH 555.9 | | | | | | EQUIPMENT GROUNDING TO BE PER 555.15 | | | | | | | | | | | | | | | | | | |
|