| 2021-04-28 13:54:35 | NEW DOCK BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21040592 |
| | |
| | 1- DESIGN CRITERIA ON DOCK CONSTRUCTION NOTES ON SHEET |
| | #2 IS MISSING THE STRUCTURE WIND EXPOSURE. ENGINEER OF |
| | RECORD TO SPECIFY ALL THE WIND DESIGN DATA, INCLUDING |
| | THE ULTIMATE AND NOMINAL WIND LOADS AND WIND EXPOSURE. |
| | SEC. R301.1 FBC-RESIDENTIAL. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: THIS STRUCTURE IS LOCATED IN EXPOSURE D. |
| | |
| | 2- ENGINEER OF RECORD TO SPECIFY THE DECKING FASTENING |
| | TO SHOW COMPLIANCE WITH THE SPECIFIED WIND DESIGN |
| | CRITERIA. |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 3- ENGINEER PLANS NEED TO HAVE A TITLE BLOCK WITH ALL |
| | THE ENGINEER'S INFORMATION AS REQUIRED BY SEC. |
| | 61G15-23.001(4) F.A.C. |
| | |
| | 4- PROVIDE SIGNED/SEALED ENGINEERING FOR THE TWO |
| | BOAT-LIFT SPECIFIED ON PLANS. ENGINEER OF RECORD TO |
| | REVIEW AND APPROVE THEM PRIOR TO SUBMITTAL. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: THIS MAY BE SUBMITTED FOR REVIEW LATER AFTER THE |
| | PERMIT IS ISSUED BUT BEFORE INSTALLATION TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 5- DOCK DRAWINGS: ELECTRONICALLY SUBMITTED DRAWINGS ARE |
| | REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE ON |
| | THEM WHEN SUBMITTING FOR PUBLIC RECORDS. |
| | YOU ALSO HAVE THE OPTION TO SUBMIT THE PAPER VERSION OF |
| | DRAWINGS WITH THE ENGINEER?S ORIGINAL HANDWRITTEN |
| | SIGNATURE AND SEAL. AFTER THE ELECTRONIC PLANS HAVE |
| | BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER |
| | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE |
| | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS |
| | REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER |
| | FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 & |
| | 61G15 |
| | |
| | 6- SURVEY NEEDS ORIGINAL SEAL/SIGNATURE AS REQUIRED BY |
| | CHAPTER 472 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR |
| | PUBLIC RECORDS. PROVIDE HARD COPY WITH ORIGINAL |
| | SEAL/SIGNATURE OR UPLOAD SURVEY WITH DIGITAL SIGNATURE. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |