2021-05-03 14:57:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A DETAIL FOR THE DOOR AND WINDOW IN-FILL.
 DETAIL IS TO SHOW STRUCTURAL COMPONENTS AND ALL
 MATERIALS, SUCH AS, INSULATION, DRYWALL, SHEATHING
 WATER BARRIER, STUCCO, ETC. FBC AMENDMENTS 107.2.1
  
 2) SPECIFY THE WIND DESIGN DATA AND THE REQUIRED
 WINDLOAD PRESSURES FOR THE WINDOWS. FBC-R301
  
 3) THE GENERAL NOTES ON SHEET A1 DO NOT APPEAR TO BE
 FOR THIS PROJECT AND IT CONTAINS ERRORS. THIS IS A
 SINGLE FAMILY RESIDENCE AND THE 2020 FBC EXISTING
 BUILDING & RESIDENTIAL ARE THE APPLICABLE CODES.
 A) (NOTE #1) THIS IS A LEVEL 2 ALTERATION AS THE AREA
 OF WORK IS LESS THAN 50 PERCENT OF THE BUILDING AREA.
 B) (NOTE #4) THIS IS A SINGLE FAMILY RESIDENCE WHICH IS
 NOT GROUP R-2.
 C) (NOTE #7) SOUND INSULATION PER FBC BUILDING 1207.3
 IS NOT REQUIRED FOR SINGLE FAMILY RESIDENCES.
 D) (NOTE #9) FIRE RATED FLOORS, CEILINGS AND WALLS ARE
 TYPICALLY NOT REQUIRED IN SINGLE FAMILY RESIDENCES.
  
 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  