| Plan Review Notes For Permit 21040584 |
| Permit Number |
21040584 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-03 14:57:33 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE A DETAIL FOR THE DOOR AND WINDOW IN-FILL. | | | DETAIL IS TO SHOW STRUCTURAL COMPONENTS AND ALL | | | MATERIALS, SUCH AS, INSULATION, DRYWALL, SHEATHING | | | WATER BARRIER, STUCCO, ETC. FBC AMENDMENTS 107.2.1 | | | | | | 2) SPECIFY THE WIND DESIGN DATA AND THE REQUIRED | | | WINDLOAD PRESSURES FOR THE WINDOWS. FBC-R301 | | | | | | 3) THE GENERAL NOTES ON SHEET A1 DO NOT APPEAR TO BE | | | FOR THIS PROJECT AND IT CONTAINS ERRORS. THIS IS A | | | SINGLE FAMILY RESIDENCE AND THE 2020 FBC EXISTING | | | BUILDING & RESIDENTIAL ARE THE APPLICABLE CODES. | | | A) (NOTE #1) THIS IS A LEVEL 2 ALTERATION AS THE AREA | | | OF WORK IS LESS THAN 50 PERCENT OF THE BUILDING AREA. | | | B) (NOTE #4) THIS IS A SINGLE FAMILY RESIDENCE WHICH IS | | | NOT GROUP R-2. | | | C) (NOTE #7) SOUND INSULATION PER FBC BUILDING 1207.3 | | | IS NOT REQUIRED FOR SINGLE FAMILY RESIDENCES. | | | D) (NOTE #9) FIRE RATED FLOORS, CEILINGS AND WALLS ARE | | | TYPICALLY NOT REQUIRED IN SINGLE FAMILY RESIDENCES. | | | | | | 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | | | | |
|