Plan Review Notes
Plan Review Notes For Permit 21040581
Permit Number 21040581
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-21 10:29:1704/21/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW THE METHOD OF PROTECTION FOR THE LP TANK
 AND APPURTENANCES PER NFPA 58. THE TANK IS BELOW
 GROUND. IT SHALL BE ANCHORED PER NFPA 58 SEC.3-2.2.7
 (H) 11. INDICATE ON THE TIE-DOWN SHEET IF THE LP TANK
 TIE-DOWN METHOD AND IF YOU ARE USING STRAPS OR CABLE,
 IF CABLE HOW IS IT PROTECTED FOR THE LP TANK AND
 APPURTENANCES PER NFPA 58 AND WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR THE
 TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO BE
 INSTALLED TO PREVENT FLOTATION PER THE NFPA 58 SEC.
 6.6.1.6.
  
 2. PLEASE CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2.
 3. PLEASE SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW
 GRADE TO COMPLY WITH NFPA 58 SEC. 6.6.6.1.
  
 4. A CATHODIC PROTECTION SYSTEM WAS SUBMITTED. PLEASE
 PROVIDE THE SIZE (LBS.) & THE NUMBER OF MAGNESIUM
 BAG(S), SIZE & TYPE OF ANODE CABLE AMOUNT OF WATER TO
 ACTIVATE IT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  