| Plan Review Notes For Permit 21040567 |
| Permit Number |
21040567 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-06 10:50:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS THAT THIS IS NG GENERATOR. | | | | | | THERE ARE NO INDICATION OF THE LOCATION, SIZE AND | | | INSTALLATION OF PIPING. | | | | | | PLEASE PROVIDE DETAILS AND EQUIPMENT SPEC SHEETS. | | | | | | | | | 1A) THERE IS NO INDICATION OF COMPLIANCE WITH NFPA 54, | | | NATIONAL FUEL GAS CODE NOR OTHER APPLICABLE NFPA CODES. | | | | | | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|