| Date |
Text |
| 2021-04-29 08:32:03 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21040564 |
| | 4/29/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE GAS PIPING AND EQUIPMENT DEMOLITION PLANS |
| | AND SUBMIT A GAS SUB-PERMIT APPLICATION- SECTIONS 105.1 |
| | & 107.2.1 FBC FG. |
| | |
| | 2) THE SCOPE OF WORK ON THE PLAN SHALL INDICATE |
| | COMPLIANCE WITH SECTION 404.15 FOR GAS PIPE CAPPING, |
| | AND SECTIONS 406.7.1.1 & 406.7.1.3 FOR GAS PIPING |
| | REMOVED FROM SERVICE REQUIREMENTS. |
| | 406.7.1.1 REMOVAL FROM SERVICE. |
| | WHERE EXISTING GAS PIPING IS OPENED, THE SECTION THAT |
| | IS OPENED SHALL BE ISOLATED FROM THE GAS SUPPLY AND THE |
| | LINE PRESSURE VENTED IN ACCORDANCE WITH SECTION |
| | 406.7.1.3. WHERE GAS PIPING MEETING THE CRITERIA OF |
| | TABLE 406.7.1.1 IS REMOVED FROM SERVICE, THE RESIDUAL |
| | FUEL GAS IN THE PIPING SHALL BE DISPLACED WITH AN INERT |
| | GAS. |
| | |
| | 406.7.1.3 OUTDOOR DISCHARGE OF PURGED GASES. |
| | THE OPEN END OF A PIPING SYSTEM BEING PRESSURE VENTED |
| | OR PURGED SHALL DISCHARGE DIRECTLY TO AN OUTDOOR |
| | LOCATION. PURGING OPERATIONS SHALL COMPLY WITH ALL OF |
| | THE FOLLOWING REQUIREMENTS: |
| | 1. 1. THE POINT OF DISCHARGE SHALL BE CONTROLLED WITH A |
| | SHUTOFF VALVE. |
| | 2. 2. THE POINT OF DISCHARGE SHALL BE LOCATED NOT LESS |
| | THAN 10 FEET FROM SOURCES OF IGNITION, NOT LESS THAN 10 |
| | FEET FROM BUILDING OPENINGS AND NOT LESS THAN 25 FEET |
| | FROM MECHANICAL AIR INTAKE OPENINGS. |
| | 3. 3. DURING DISCHARGE, THE OPEN POINT OF DISCHARGE |
| | SHALL BE CONTINUOUSLY ATTENDED AND MONITORED WITH A |
| | COMBUSTIBLE GAS INDICATOR THAT COMPLIES WITH SECTION |
| | 406.7.1.4. |
| | 4. 4. PURGING OPERATIONS INTRODUCING FUEL GAS SHALL BE |
| | STOPPED WHEN 90 PERCENT FUEL GAS BY VOLUME IS DETECTED |
| | WITHIN THE PIPE. |
| | 5. 5. PERSONS NOT INVOLVED IN THE PURGING OPERATIONS |
| | SHALL BE EVACUATED FROM ALL AREAS WITHIN 10 FEET (3048 |
| | MM) OF THE POINT OF DISCHARGE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |
| 2021-04-23 13:09:45 | DO THEY NEED A GAS PERMIT TO DISCONNECT ALL THE OLD |
| | LIGHT POLES (GAS). |