| 2021-06-22 14:13:38 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE A DRAWING OF THE PAD THAT THE HEATERS WILL | | | BE ANCHORED TO IN ORDER TO RESIST WIND LOADS. PROVIDE | | | THE DIMENSIONS OF THE PAD AND REINFORCING IF REQUIRED. | | | SPECIFY THE ANCHORS THAT WIIL BE USED TO ATTACH THE | | | HEATER TO THE SLAB AND WHERE THEY WILL BE LOCATED. FBC | | | CHAPTER 16. IF PREFABRICATED SLABS ARE USED, SUBMIT | | | SITE SPECIFIC ENGINEERING THAT HAS BEEN DIGITALLY | | | SIGNED AND SEALED BY THE ENGINEER. FBC AMEND. 107.1 |
|