2021-06-22 14:13:38PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A DRAWING OF THE PAD THAT THE HEATERS WILL
 BE ANCHORED TO IN ORDER TO RESIST WIND LOADS. PROVIDE
 THE DIMENSIONS OF THE PAD AND REINFORCING IF REQUIRED.
 SPECIFY THE ANCHORS THAT WIIL BE USED TO ATTACH THE
 HEATER TO THE SLAB AND WHERE THEY WILL BE LOCATED. FBC
 CHAPTER 16. IF PREFABRICATED SLABS ARE USED, SUBMIT
 SITE SPECIFIC ENGINEERING THAT HAS BEEN DIGITALLY
 SIGNED AND SEALED BY THE ENGINEER. FBC AMEND. 107.1