2021-04-26 14:45:112ND REVIEW FBC-2017 RES.
 PERMIT- 21040496
 4/26/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 6TH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST- PROVIDE A DIMENSIONED FLOOR PLAN
 DRAWING AT MINIMUM 1/8 IN. SCALE AND A REVISED SANITARY
 ISOMETRIC- SECTION 107.2.1 WPB. PLEASE IDENTIFY ALL
 FIXTURES AND CABINETRY IN THE DRAWING. IT APPEARS TO
 SHOW A LAV SINK, TOILET, AND LONG VANITY CABINET WITH
 NO SINK. PLEASE INDICATE THE WIDTH OF THE CABINET TO
 VERIFY ADEQUATE SPACE WILL BE PROVIDED FOR THE LAV AND
 TOILET- SEE FIGURE R307 FBC RES. PLEASE SUBMIT A
 REVISED SANITARY RISER DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  