2021-06-09 09:52:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT RESOLVED. THE DOCUMENTS THAT WERE SUBMITTED ARE
 FOR A MECHANICAL STAND, NOT A GENERATOR. THE DRAWINGS
 ARE ILLEGIBLE. THE DRAWINGS ARE GENERAC AND THE ITEMS
 THAT ARE SPECIFIC TO THIS PROJECT ARE NOT INDICATED BY
 BEING CIRCLED OR HI-LIGHTED. NO DETAILS FOR THE
 EXISTING CONCRETE SLAB WERE PROVIDED.] PROVIDE DETAILS
 OF THE EXISTING GENERATOR SLAB (SIZE, THICKNESS AND
 MATERIAL) AND SPECIFY THE TYPE AND NUMBER OF FASTENERS
 THAT WILL BE USED TO ANCHOR THE GENERATOR TO RESIST
 WIND LOADS. FBC 107.2.1
  
 2) [ NOT RESOLVED. THIS REQUIREMENT HAS NOT BEEN
 SPECIFIED ON THE SITE PLAN AS REQUESTED.] THE GENERATOR
 EXHAUST IS REQUIRED TO BE AT LEAST 10 FEET FROM ANY
 OPENINGS INTO A BUILDING. SPECIFY THIS ON THE LOCATION
 SURVEY. R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
  