| 2021-04-22 21:41:43 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21040407 |
| | 4/22/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1- TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 2- SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC. |
| | 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| | 3- SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES |
| | SECS. G2413.4.1, G2413.4.2. |
| | 4- SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 5- INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020 |
| | FBC FUEL GAS RES. SEC. G2413.2. |
| | 6- SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR |
| | 2020 FBC FUEL GAS RES. SEC. G2408.1. |
| | 7- SUBMIT SIZING TABLE USED IN THE DESIGN FOR THE GAS |
| | SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING |
| | THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD |
| | THAT WERE USED IN THE DESIGN OF THIS SYSTEM 2020 FBC |
| | FUEL GAS SEC. 402.3 OR 2020 FBC FUEL GAS RES. SEC. |
| | G2413.3 |
| | 8- SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| | FUEL GAS RES. SEC. G2421.1. |
| | 9- GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| | SEC. 107.3.5.3 (12) RESIDENTIAL GAS |
| | 10- THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?) |
| | FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE, |
| | EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS |
| | OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION |
| | INSTRUCTIONS. |
| | 11- THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR |
| | SHALL BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR |
| | SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE |
| | GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |