2021-04-29 14:36:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE DETAILS OF THE EXISTING GENERATOR SLAB
 (SIZE, THICKNESS AND MATERIAL) AND SPECIFY THE TYPE AND
 NUMBER OF FASTENERS THAT WILL BE USED TO ANCHOR THE
 GENERATOR TO RESIST WIND LOADS. FBC 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. SPECIFY THIS ON
 THE LOCATION SURVEY. R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
  