| Notes |
| Date |
Text |
| 2021-04-29 14:36:15 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE DETAILS OF THE EXISTING GENERATOR SLAB | | | (SIZE, THICKNESS AND MATERIAL) AND SPECIFY THE TYPE AND | | | NUMBER OF FASTENERS THAT WILL BE USED TO ANCHOR THE | | | GENERATOR TO RESIST WIND LOADS. FBC 107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. SPECIFY THIS ON | | | THE LOCATION SURVEY. R303.5.1 INTAKE OPENINGS. | | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | | AND LOADING DOCKS. | | | | | | |
|