2021-07-07 16:13:004TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21040400
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M002: YOU MAY USE ASHRAE 62.1 AS AN ALTERNATE
 MEANS AND METHODS FOR VENTILATION CALCULATIONS, BUT YOU
 MUST SHOW YOUR CALCULATIONS. PLEASE PROVIDE THE
 CALCULATIONS FOR THE BI-POLAR IONIZATION. FBC M 403.2
 (EXCEPTION)
  
 2) IF THERE IS ANY DUCTWORK THAT IS NOW GOING TO BE
 EXISTING (REUSED FROM EXISTING SYSTEM) PLEASE INDICATE
 THAT DUCTWORK ON THE DRAWINGS. FBC 107.2.1
  
 3) PLEASE SHOW ALL DAMPER PROTECTION AT DUCT
 PENETRATIONS OF RATED WALLS. FBC M 607
  
 4) PLEASE PROVIDE A RATED WALL GUIDE I.E. ONE HOUR
 RATED, TWO HOUR RATED, FIRE PARTITION, FIRE WALL, SMOKE
 RATED. FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728