| Plan Review Notes For Permit 21040400 |
| Permit Number |
21040400 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-07-07 16:13:00 | 4TH REVIEW FBC-2020 MECHANICAL | | | PERMIT-21040400 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M002: YOU MAY USE ASHRAE 62.1 AS AN ALTERNATE | | | MEANS AND METHODS FOR VENTILATION CALCULATIONS, BUT YOU | | | MUST SHOW YOUR CALCULATIONS. PLEASE PROVIDE THE | | | CALCULATIONS FOR THE BI-POLAR IONIZATION. FBC M 403.2 | | | (EXCEPTION) | | | | | | 2) IF THERE IS ANY DUCTWORK THAT IS NOW GOING TO BE | | | EXISTING (REUSED FROM EXISTING SYSTEM) PLEASE INDICATE | | | THAT DUCTWORK ON THE DRAWINGS. FBC 107.2.1 | | | | | | 3) PLEASE SHOW ALL DAMPER PROTECTION AT DUCT | | | PENETRATIONS OF RATED WALLS. FBC M 607 | | | | | | 4) PLEASE PROVIDE A RATED WALL GUIDE I.E. ONE HOUR | | | RATED, TWO HOUR RATED, FIRE PARTITION, FIRE WALL, SMOKE | | | RATED. FBC 107.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|