Plan Review Notes
Plan Review Notes For Permit 21040400
Permit Number 21040400
Review Stop M
Sequence Number 3
Notes
Date Text
2021-06-04 08:25:362ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21040400
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I DO NOT SEE ANY SCOPE OF WORK FOR A GENERAL
 CONTRACTOR. PLEASE SHOW WHY A G.C. HAS APPLIED FOR A
 PERMIT FOR MECHANICAL WORK. ALSO PLEASE HAVE A FLORIDA
 LICENSED MECHANICAL CONTRACTOR APPLY FOR A MECHANICAL
 PERMIT FOR THIS PROJECT.
  
 2) PLEASE SHOW THE RATED WALLS IN THIS BUILDING AND HOW
 THE PENETRATIONS IN THE RATED WALLS BY THE DUCT WORK
 WILL BE PROTECTED(FIRE DAMPERS AND FIRE SMOKE DAMPERS)
 FBC M 607
  
 3) SHEET M002: WE ARE CURRENTLY UNDER THE 2020 7TH
 EDITION FBC M PLEASE LABEL THIS OUTDOOR AIR USING THE
 LATEST CODE.
  
 4) SHEET M002: THE OUTDOOR AIR CALCULATIONS ARE VERY
 LOW. PLEASE USE FBC M 403.3.1.1 AND TABLE 403.3.1.1 AND
 NOT THE ARCHITECTURAL OCCUPANT LOAD FOR SPACES TO
 CALCULATE THE OUTDOOR AIR REQUIRED FOR EACH USE OF
 SPACE.
  
 5) SHEET M002: PLEASE LABEL ?SPACE USE CLASSIFICATION?
 BASED ON TABLE 403.3.1.1 (EXAMPLE- WEST TECH
 POSITION-EAST TECH POSITION)
  
 6) SHEET M101 & M102: PLEASE PROVIDE A DETAIL DRAWING
 OF THE 1 INCH CONDENSATE LINE CONNECTING TO THE
 EXISTING STORM WATER PIPING (NOTE 3).
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  