| 2021-06-04 08:25:36 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21040400 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) I DO NOT SEE ANY SCOPE OF WORK FOR A GENERAL |
| | CONTRACTOR. PLEASE SHOW WHY A G.C. HAS APPLIED FOR A |
| | PERMIT FOR MECHANICAL WORK. ALSO PLEASE HAVE A FLORIDA |
| | LICENSED MECHANICAL CONTRACTOR APPLY FOR A MECHANICAL |
| | PERMIT FOR THIS PROJECT. |
| | |
| | 2) PLEASE SHOW THE RATED WALLS IN THIS BUILDING AND HOW |
| | THE PENETRATIONS IN THE RATED WALLS BY THE DUCT WORK |
| | WILL BE PROTECTED(FIRE DAMPERS AND FIRE SMOKE DAMPERS) |
| | FBC M 607 |
| | |
| | 3) SHEET M002: WE ARE CURRENTLY UNDER THE 2020 7TH |
| | EDITION FBC M PLEASE LABEL THIS OUTDOOR AIR USING THE |
| | LATEST CODE. |
| | |
| | 4) SHEET M002: THE OUTDOOR AIR CALCULATIONS ARE VERY |
| | LOW. PLEASE USE FBC M 403.3.1.1 AND TABLE 403.3.1.1 AND |
| | NOT THE ARCHITECTURAL OCCUPANT LOAD FOR SPACES TO |
| | CALCULATE THE OUTDOOR AIR REQUIRED FOR EACH USE OF |
| | SPACE. |
| | |
| | 5) SHEET M002: PLEASE LABEL ?SPACE USE CLASSIFICATION? |
| | BASED ON TABLE 403.3.1.1 (EXAMPLE- WEST TECH |
| | POSITION-EAST TECH POSITION) |
| | |
| | 6) SHEET M101 & M102: PLEASE PROVIDE A DETAIL DRAWING |
| | OF THE 1 INCH CONDENSATE LINE CONNECTING TO THE |
| | EXISTING STORM WATER PIPING (NOTE 3). |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |