2021-07-30 11:01:59AC DUCT REPLACEMENT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWINGS NEED TO SHOW ALL FIRE AND SMOKE WALLS -
 PROVIDED DRAWINGS DO NOT SHOW ALL FIRE RATED WALLS (YOU
 CAN REQUEST A RECORDS SEARCH - HTTPS://WESTPALMBEACHFL.
 GOVQA.US/WEBAPP/_RS/(S(JYNBG4BW3AQKIWM33ZN5FYNB))/SUPPO
 RTHOME.ASPX )
 2) PLEASE SHOW ALL FIRE RATED WALL AND FLOOR
 (HORIZONTAL ASSEMBLIES) PENETRATION DETAILS PER FBC
 714.1.1DUCTS AND AIR TRANSFER OPENINGS.
 PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS
 THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH
 SECTIONS 714.3 THROUGH 714.4.3. PENETRATIONS OF
 HORIZONTAL ASSEMBLIES NOT PROTECTED WITH A SHAFT AS
 PERMITTED BY SECTION 717.6, AND NOT REQUIRED TO BE
 PROTECTED WITH FIRE DAMPERS BY OTHER SECTIONS OF THIS
 CODE, SHALL COMPLY WITH SECTIONS 714.5 THROUGH 714.6.2.
 DUCTS AND AIR TRANSFER OPENINGS THAT ARE PROTECTED WITH
 DAMPERS SHALL COMPLY WITH SECTION 717.