| Plan Review Notes For Permit 21040400 |
| Permit Number |
21040400 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-04-26 10:51:09 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21040400 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A COMPLETE MECHANICAL EQUIPMENT | | | SIZING CALCULATION INCLUDING ALL OF THE AHU?S. FBC EC | | | 403 | | | | | | 2) THE CONDENSATE FROM THE AHU?S CANNOT DRAIN INTO THE | | | BUILDING DRAIN, IT MUST DRAIN TO STORM DRAINAGE OR AN | | | APPROVED PLACE AT THE EXTERIOR OF THE BUILDING. FBC M | | | 307.2.1 | | | | | | 3) SHEET M103: THE CU-1 MUST ALSO HAVE A GUARD TO | | | PROTECT WORKERS FROM FALLING AS THEY MAINTAIN THE UNIT. | | | FBC M 304.11 | | | | | | 4) PLEASE SHOW ROOF ACCESS ON THE DRAWINGS FOR SERVICE | | | OF THE RTU?S. FBC M 306.5 | | | | | | 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | | USE OF SPACE IN THIS BUILDING. FBC M 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|