| 2021-04-28 13:32:35 | NEW 2 STORY APT. BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE PROVIDE ROOF TOP GUARD RAIL DETAILS FROM A |
| | DESIGN PROFESSIONAL TO COMPLY WITH REQUIRED LOADS PER |
| | FBC 1607.8.1 - - 1607.8.1.1 |
| | 2) GUARD REQUIREMENTS - 1015.6 MECHANICAL EQUIPMENT, |
| | SYSTEMS AND DEVICES. |
| | GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND |
| | EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE |
| | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| | INCHES (533 MM) IN DIAMETER. |
| | 3) PLEASE PROVIDE DETAILS FROM A DESIGN PROFESSIONAL |
| | FOR THE MECHANICAL EQUIPMENT STANDS AND CURBS OR |
| | PROVIDE THE MIAMI DADE OR FLORIDA STATE PRODUCT |
| | APPROVAL TO COMPLY WITH THE REQUIRED WIND LOADS PER FBC |
| | 1609 AND NOTE NUMBER 4 ON DRAWING M001. |
| | 4) PLEASE PROVIDE DETAILS FROM A DESIGN PROFESSIONAL |
| | FOR THE MECHANICAL BEAM SUPPORT ON DRAWING M102 NOTE |
| | NUMBER 8. |
| | 5) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR DESIGN |
| | ON ANY ADDED DETAILS FBC 1603.1.4 |