Plan Review Notes
Plan Review Notes For Permit 21040400
Permit Number 21040400
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-28 13:32:35NEW 2 STORY APT. BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE ROOF TOP GUARD RAIL DETAILS FROM A
 DESIGN PROFESSIONAL TO COMPLY WITH REQUIRED LOADS PER
 FBC 1607.8.1 - - 1607.8.1.1
 2) GUARD REQUIREMENTS - 1015.6 MECHANICAL EQUIPMENT,
 SYSTEMS AND DEVICES.
 GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND
 EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
 3) PLEASE PROVIDE DETAILS FROM A DESIGN PROFESSIONAL
 FOR THE MECHANICAL EQUIPMENT STANDS AND CURBS OR
 PROVIDE THE MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVAL TO COMPLY WITH THE REQUIRED WIND LOADS PER FBC
 1609 AND NOTE NUMBER 4 ON DRAWING M001.
 4) PLEASE PROVIDE DETAILS FROM A DESIGN PROFESSIONAL
 FOR THE MECHANICAL BEAM SUPPORT ON DRAWING M102 NOTE
 NUMBER 8.
 5) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR DESIGN
 ON ANY ADDED DETAILS FBC 1603.1.4