2021-04-09 07:35:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL PLAN DOES NOT SHOW THE REQUIRED OUTLETS ON
 THE ISLAND. PLEASE INDICATE ALL NEW OUTLETS ON ISLAND
 PLAN. 210.52
  
 ISLAND COUNTERTOP SPACES. AT LEAST ONE RECEPTACLE SHALL
 BE INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH A
 LONG DIMENSION OF 600 MM (24 IN.) OR GREATER AND A
 SHORT DIMENSION OF 300 MM (12 IN.) OR GREATER.
  
 SEPARATE SPACES. COUNTERTOP SPACES SEPARATED BY
 RANGETOPS, REFRIGERATORS, OR SINKS SHALL BE CONSIDERED
 AS SEPARATE COUNTERTOP SPACES IN APPLYING THE
 REQUIREMENTS OF 210.52(C)(1). IF A RANGE,
 COUNTER-MOUNTED COOKING UNIT, OR SINK IS INSTALLED IN
 AN ISLAND OR PENINSULAR COUNTERTOP AND THE DEPTH OF THE
 COUNTERTOP BEHIND THE RANGE, COUNTER-MOUNTED COOKING
 UNIT, OR SINK IS LESS THAN 300 MM (12 IN.), THE RANGE,
 COUNTER-MOUNTED COOKING UNIT, OR SINK SHALL BE
 CONSIDERED TO DIVIDE THE COUNTERTOP SPACE INTO TWO
 SEPARATE COUNTERTOP SPACES. EACH SEPARATE COUNTERTOP
 SPACE SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS IN
 210.52(C).