| Plan Review Notes For Permit 21040385 |
| Permit Number |
21040385 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-09 07:35:37 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ELECTRICAL PLAN DOES NOT SHOW THE REQUIRED OUTLETS ON | | | THE ISLAND. PLEASE INDICATE ALL NEW OUTLETS ON ISLAND | | | PLAN. 210.52 | | | | | | ISLAND COUNTERTOP SPACES. AT LEAST ONE RECEPTACLE SHALL | | | BE INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH A | | | LONG DIMENSION OF 600 MM (24 IN.) OR GREATER AND A | | | SHORT DIMENSION OF 300 MM (12 IN.) OR GREATER. | | | | | | SEPARATE SPACES. COUNTERTOP SPACES SEPARATED BY | | | RANGETOPS, REFRIGERATORS, OR SINKS SHALL BE CONSIDERED | | | AS SEPARATE COUNTERTOP SPACES IN APPLYING THE | | | REQUIREMENTS OF 210.52(C)(1). IF A RANGE, | | | COUNTER-MOUNTED COOKING UNIT, OR SINK IS INSTALLED IN | | | AN ISLAND OR PENINSULAR COUNTERTOP AND THE DEPTH OF THE | | | COUNTERTOP BEHIND THE RANGE, COUNTER-MOUNTED COOKING | | | UNIT, OR SINK IS LESS THAN 300 MM (12 IN.), THE RANGE, | | | COUNTER-MOUNTED COOKING UNIT, OR SINK SHALL BE | | | CONSIDERED TO DIVIDE THE COUNTERTOP SPACE INTO TWO | | | SEPARATE COUNTERTOP SPACES. EACH SEPARATE COUNTERTOP | | | SPACE SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS IN | | | 210.52(C). |
|