| Plan Review Notes For Permit 21040327 |
| Permit Number |
21040327 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-23 12:09:05 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A COPY OF A BOUNDARY SURVEY OF THE PROPERTY | | | FOR COMPARISON WITH THE SITE PLAN. FBC 107.2.5 | | | | | | 2) THE PRODUCT APPROVAL (FL-17184.2) FOR THE 5' X 8' | | | DOUBLE OUTSWING FRENCH DOORS HAS A MAXIMUM DESIGN | | | PRESSURE OF -45 PSF. THE DOOR PRESSURE SCHEDULE ON | | | SHEET S.0 HAS THE REQUIRED WIND LOAD PRESSURE AS -52.27 | | | PSF. SUBMIT A PRODUCT APPROVAL FOR THESE DOORS WITH AN | | | ADEQUATE DESIGN PRESSURE. FBC AMEND. 107.3.4 | | | | | | 3) THE DESIGN PRESSURES IN THE GAF MODIFIED BITUMEN | | | ROOFING PRODUCT APPROVAL (NOA NO. 18-0919.12) ARE NOT | | | ADEQUATE FOR ALL OF THIS STRUCTURE'S ROOF ZONES. | | | SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES, FASTENING | | | OPTION AND DESIGN PRESSURE WILL BE INSTALLED. SELECT | | | ONE THAT ALLOWS ENHANCED FASTENING TO INCREASE THE | | | DESIGN PRESSURES AND SUBMIT SIGNED AND SEALED RAS 117 | | | ENHANCED FASTENING CALCULATIONS. FBC AMEND. 107.1 | | | |
|