2021-04-23 13:06:151ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21031243
 4/22/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P0.2 GAS RISER- PLEASE PROVIDE THE FOLLOWING
 LIST OF INFORMATION PER FBC RES. FUEL GAS
  
 A) DELIVERY PRESSURES AT FIRST AND SECOND STAGE
 REGULATORS- SECTIONS G2413.2 & G2421.2.
  
 C) TOTAL BTU LOAD- G2413.2
  
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET- G2413.4.1.
  
 E) LOCATIONS AND TYPES OF PIPE SLEEVES- G2415.1.
  
 F) EHD OF THE CSST PIPING- G413.3 & G2415.2.
  
 G) SHOW THE REQUIRED UNIONS PIPE UNIONS WITHIN 1 FT. OF
 EITHER SIDE OF THE REGULATORS CONNECTED TO RIGID
 PIPING- G2421.2(7).
  
 H) LIST THE PIPE SIZING TABLES OR PIPE SIZING METHOD
 USED- G2413.3.
  
 2) P0.2 & P1.1: PROVIDE A TRACER WIRE FOR THE UG PE
 PIPING PER SECTION G2415.17.3. A YELLOW INSULATED
 COPPER TRACER WIRE OR OTHER APPROVED CONDUCTOR, OR A
 PRODUCT SPECIFICALLY DESIGNED FOR THAT PURPOSE, SHALL
 BE INSTALLED ADJACENT TO UNDERGROUND NONMETALLIC
 PIPING. THE TRACER WIRE SIZE SHALL NOT BE LESS THAN 18
 AWG AND THE INSULATION TYPE SHALL BE SUITABLE FOR
 DIRECT BURIAL.
  
 3) P0.2 & P1.1: PROVIDE COMBUSTION AIR CALCULATIONS AND
 INDICATE HOW THE AIR WILL BE PROVIDED TO THE GAS RANGE-
 SECTION- G2407.1 FBC RES.
  
 4) P0.2 & P1.1: PROVIDE MAKEUP AIR FOR THE DRYER AND
 INDICATE HOW THE MAKEUP AIR WILL BE PROVIDED- G2439.5
 FBC RES.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 FIRED APPLIANCES- SECTION G2408.1 FBC RES.
  
 6) SUBMIT A GAS SUB-PERMIT IF THE INSTALLATIONS ARE TO
 BE INCLUDED UNDER THE MASTER PERMIT- SECTION 105.1 WPB.
 IF THE GAS INSTALLATIONS ARE TO BE UNDER A SEPARATE
 PRIMARY PERMIT, PLEASE PLACE A NOTE ON THE PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  