| 2021-04-23 13:06:15 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21031243 |
| | 4/22/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P0.2 GAS RISER- PLEASE PROVIDE THE FOLLOWING |
| | LIST OF INFORMATION PER FBC RES. FUEL GAS |
| | |
| | A) DELIVERY PRESSURES AT FIRST AND SECOND STAGE |
| | REGULATORS- SECTIONS G2413.2 & G2421.2. |
| | |
| | C) TOTAL BTU LOAD- G2413.2 |
| | |
| | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET- G2413.4.1. |
| | |
| | E) LOCATIONS AND TYPES OF PIPE SLEEVES- G2415.1. |
| | |
| | F) EHD OF THE CSST PIPING- G413.3 & G2415.2. |
| | |
| | G) SHOW THE REQUIRED UNIONS PIPE UNIONS WITHIN 1 FT. OF |
| | EITHER SIDE OF THE REGULATORS CONNECTED TO RIGID |
| | PIPING- G2421.2(7). |
| | |
| | H) LIST THE PIPE SIZING TABLES OR PIPE SIZING METHOD |
| | USED- G2413.3. |
| | |
| | 2) P0.2 & P1.1: PROVIDE A TRACER WIRE FOR THE UG PE |
| | PIPING PER SECTION G2415.17.3. A YELLOW INSULATED |
| | COPPER TRACER WIRE OR OTHER APPROVED CONDUCTOR, OR A |
| | PRODUCT SPECIFICALLY DESIGNED FOR THAT PURPOSE, SHALL |
| | BE INSTALLED ADJACENT TO UNDERGROUND NONMETALLIC |
| | PIPING. THE TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 |
| | AWG AND THE INSULATION TYPE SHALL BE SUITABLE FOR |
| | DIRECT BURIAL. |
| | |
| | 3) P0.2 & P1.1: PROVIDE COMBUSTION AIR CALCULATIONS AND |
| | INDICATE HOW THE AIR WILL BE PROVIDED TO THE GAS RANGE- |
| | SECTION- G2407.1 FBC RES. |
| | |
| | 4) P0.2 & P1.1: PROVIDE MAKEUP AIR FOR THE DRYER AND |
| | INDICATE HOW THE MAKEUP AIR WILL BE PROVIDED- G2439.5 |
| | FBC RES. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS |
| | FIRED APPLIANCES- SECTION G2408.1 FBC RES. |
| | |
| | 6) SUBMIT A GAS SUB-PERMIT IF THE INSTALLATIONS ARE TO |
| | BE INCLUDED UNDER THE MASTER PERMIT- SECTION 105.1 WPB. |
| | IF THE GAS INSTALLATIONS ARE TO BE UNDER A SEPARATE |
| | PRIMARY PERMIT, PLEASE PLACE A NOTE ON THE PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |